"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group

Coding
Coding in the factory set condition
Priority DHW heating
A2:2
DHW tank priority applicable to heating circuit
pump and mixing valve.
Economy function outside temperature
A5:5
With heating circuit pump logic function
(economy circuit): Heating circuit pump "OFF"
when the outside temperature (AT) is 1 K
higher than the set room temperature (RT
AT > RT
+ 1 K
set
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Coding in the factory set condition
Extended economy function mixing valve
A7:0
Only for heating circuits with mixing valve:
Without mixing valve economy function.
Pump idle time, transition reduced mode. Operation
A9:7
With pump idle time (heating circuit pump
"OFF").
(See function description on page 51).
)
set
With heating circuit pump logic function: Heating circuit pump "OFF"
AT > RT
+ 5 K
set
AT > RT
+ 4 K
set
AT > RT
+ 3 K
set
AT > RT
+ 2 K
set
AT > RT
+ 1 K
set
AT > RT
set
AT > RT
- 1 K
set
AT > RT
- 9 K
set
Possible change
A2:0
Without DHW tank priority applicable to
heating circuit pump and mixing valve.
A2:1
DHW tank priority applies only to the
mixing valves.
A5:0
Without heating circuit pump logic
function.
A5:1
With heating circuit pump logic function:
to
Heating circuit pump "OFF"; see the
A5:15
following table.
Possible change
A7:1
With mixing valve economy function (extended
heating circuit pump logic):
Heating circuit pump also "OFF":
- If the mixing valve has been closed for
longer than 20 min.
Heating circuit pump "ON":
- If the mixing valve changes to control
function.
- If there is a risk of frost.
A9:0
Without pump idle time.
A9:1
With pump idle time; adjustable from 1 to 15.
to
1: short idle period
A9:15
15: long idle period
Code 1, Vitotronic 300-K