Viessmann VITOTRONIC 300 Installation And Service Instructions Manual page 94

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Code 2, Vitotronic 300-K
"DHW" Group
Coding in the factory set condition
62:10
Circulation pump with a run-on time after DHW
tank heating of max. 10 min.
64:2
During party mode and after external changeover
to constant operation with the standard room
temperature:
Constant DHW heating enabled and DHW
circulation pump "ON".
66:4
Input of the set DHW temperature:
At the control unit programming unit and all
installed Vitotrol 300A remote controls.
67:40
For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected set
temperature (DHW heating by the boiler only if
solar energy is not sufficient).
68:8
With 2 DHW tank temperature sensors
(code "55:2"):
DHW tank heating stop point at set value x 0.8.
69:7
With 2 DHW tank temperature sensors
(code "55:2"):
DHW tank heating start point at set value x 0.7.
6A:75
Runtime, servomotor, mixing valve, heat
exchanger set, Vitotrans 222, (80 and 120 kW):
75 sec.
70:0
DHW circulation pump "ON" according to time
program when DHW heating is enabled.
71:0
DHW circulation pump:
"ON" according to time program.
72:0
DHW circulation pump:
"ON" according to time program.
73:0
DHW circulation pump:
"ON" according to time program.
75:0
DHW circulation pump "ON" during economy
mode according to time program.
94
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Possible change
62:0
Circulation pump without run-on.
62:1
Run-on time adjustable from 1 to 15 min.
to
62:15
64:0
No DHW heating, DHW circulation pump "OFF".
64:1
DHW heating and DHW circulation pump
according to time program.
66:0
At the control unit programming unit.
66:1
At the control unit programming unit and remote
control system circuit A1 (heating circuit ).
66:2
At the control unit programming unit and
remote control heating circuit with mixing valve
M2 (heating circuit 2).
66:3
At the control unit programming unit and
remote control heating circuit with mixing valve
M3 (heating circuit 3).
66:5
At the remote control system circuit A1
(heating circuit 1).
66:6
At the remote control heating circuit with
mixing valve M2 (heating circuit 2).
66:7
At the remote control heating circuit with
mixing valve M3 (heating circuit 3).
67:0
No third set value.
67:10
Set DHW temperature adjustable from 50 to
to
194° F (10 to 95° C). (limited by boiler specific
67:95
parameters).
Observe the setting of coding address "56".
68:2
Factor adjustable from 0.2 to 1;
to
1 step
0.1
68:10
69:1
Factor adjustable from 0.1 to 0.9;
to
1 step
0.1
69:9
6A:10
For heat exchanger set Vitotrans 222 (240 kW):
to
set 113 sec.
6A:255
Runtime adjustable from 10 to 255 sec.
70:1
DHW circulation pump "ON" according to time
program.
71:1
"OFF" during DHW heating to the first set value.
71:2
"ON" during DHW heating to the first set value.
72:1
"OFF" during DHW heating to the second set
value.
72:2
"ON" during DHW heating to the second set
value.
73:1
"ON" from once per hour for 5 min. up to
to
6 times per hour for 5 min. during the time
73:6
program.
73:7
Constantly "ON".
75:1
DHW circulation pump "OFF" during economy
mode.