Code 2, Vitotronic 300-K
"General" Group
Coding in the factory set condition
4D:1
Connection at plug sL:
Shunt pump.
4E:1
Connection at plug gSA1:
3-way mixing valve for return temperature
control.
4F:5
Run-on time, shunt or distribution pump 5 min.
54:0
Without solar thermal system.
5B:0
Without extension EA1.
5C:0
Function output aBJ at extension EA1:
Central fault message.
5D:0
Function input DE1 at extension EA1:
No function.
5E:0
Function input DE2 at extension EA1:
No function.
88
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Possible change
4D:0
Distribution pump.
4E:2
Motor for 3-way mixing valve, primary store
system.
4F:0
No pump run-on.
4F:1
Run-on time adjustable from 1 to 60 min.
to
4F:60
54:1
With Vitosolic 100; automatic recognition.
54:2
With Vitosolic 200; automatic recognition.
54:3
With solar control module, type SM1, without
auxiliary function; automatic recognition.
54:4
With solar control module, type SM1, with
auxiliary function, e.g. central heating backup;
automatic recognition.
5B:1
With extension EA1; automatic recognition.
5C:1
Accessories pump.
5C:2
No function.
5C:3
Heating circuit pump A1 is switched to low
speed (reduced mode).
5C:4
Heating circuit pump M2 is switched to low
speed (reduced mode).
5C:5
Heating circuit pump M3 is switched to low
speed (reduced mode).
5D:1
Heating program changeover.
5D:2
External demand with minimum set supply
temperature.
Selection of set value in coding address "9B"
in the "General" group.
5D:3
External blocking.
5D:4
External blocking with fault message.
5D:5
Fault message input.
5D:6
Brief operation, DHW circulation pump
(pushbutton function).
Setting of runtime for DHW circulation pump
in coding address "12" in the "General" group.
5E:1
Heating program changeover.
5E:2
External demand with minimum set supply
temperature.
Selection of set value in coding address "9B"
in the "General" group.
5E:3
External blocking.
5E:4
External blocking with fault message.
5E:5
Fault message input.
5E:6
Brief operation, DHW circulation pump
(pushbutton function).
Setting of runtime for DHW circulation pump in
coding address "12" in the "General" group.