Vertical Side Wall Application & Installation - Majestic 360DVS2 Installation Instructions & Homeowner's Manual

360 dvs series direct vent fireplaces
Table of Contents

Advertisement

360 DVS Series Direct Vent Fireplaces
Vent Opening for Combustible Wall
9³⁄₈"
(240mm)
10³⁄₈"
(265mm)
Vent Opening for Noncombustible Wall
7¹⁄₂"
(190mm)
Fig. 18 Locate vent opening on rear wall.
#8 Screws (2)
CFM135a
Fig. 19 Adjustable zero clearance sleeve.
STEP 3
Measure the horizontal length requirement for the
venting including a 2" (51mm) overlap, i.e. from the
elbow to the outside wall face plus 2" (51mm), or the
distance required if installing a second 90˚ elbow.
(Fig. 20)
STEP 4
Install the 4" (102mm) vent to the appliance collar
and secure with three (3) sheetmetal screws. Install the
7" (178mm) vent pipe to the appliance collar and
secure with three (3) sheetmetal screws. It is not
necessary to seal this connection.
It is critical there be no downward slope
away from the appliance when connect-
ing the vent or elbow.
16
Framing Detail
VO584-100
Maximum
Length
12" (305mm)
#8 Screws (2)
Firestop
Side View
STEP 5
Guide vent through the vent hole as you place the
appliance in its installed position. Guide the 4"
(102mm) and 7" (178mm) collars of the vent termina-
tion into the outer ends of the venting.
Do not force the termination. If the vent pipes do not
align with the termination, remove and realign the
venting at the appliance flue collars.
Attach the termination to the wall as outlined in the
instruction sheet supplied with the termination.
Vertical Sidewall Application
It is very important the venting system maintain its
balance between the combustion air intake and the flue
gas exhaust, certain limitations concerning vent con-
figurations must be strictly adhered to.
The vent graph (Fig. 16), showing relationship
between vertical and horizontal side wall venting, will
help determine allowable dimensions.
Minimum clearance between vent pipes and com-
bustible materials is 1" (25 mm) on top, bottom, and
sides, unless otherwise noted.
When the vent termination exits through foundations
less than 20" (508mm) below siding outcrop, the
vent pipe must flush up with the siding.
It is best to locate the fireplace in such a way that
minimizes the number of offsets and horizontal vent
length. The horizontal vent run refers to the total
length of vent pipe from the flue collar of the fire-
place to the face of the outer wall.
NOTE: When installing the appliance as a rear vent
unit, the 90˚ transition elbow attached directly to the
rear of the unit is not included in the following criteria
and calculations. Unless it is specifically mentioned, this
elbow should be ignored when calculating venting
layouts.
Fig. 20 Maximum three (3) 90° elbows per installation.
FP1435
10006326

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents