Appendix B: Ul Listed Commercial And Residential Installations - DSC PowerSeries PC1616 Installation Manual

V4.6 na security system
Hide thumbs Also See for PowerSeries PC1616:
Table of Contents

Advertisement

Appendix B: UL Listed Commercial and Residential Installations

The control panel model PC1616/PC1832/PC1864 has been tested and found in com-
pliance with the following standard:
UL1610
Central-Station Burglar-Alarm Units
UL365
Police Station Connected Burglar Alarm Units and Systems
UL1023
Household Burglar-Alarm System Units
UL985
Household Fire Warning System Units
UL1635
Digital Alarm Communicator System Units
ULC-S304-06
Signal Receiving Centre & Premise Burglar Alarm Control Units
ULC-S559-04
Equipment for Fire Signal Receiving Centres and Systems
ULC-S545-02
Residential Fire Warning System Control Units
ORD-C1023-1974 Household Burglar-Alarm System Units
This product has also been tested and found in compliance with the ANSI/SIA CP-
01-2000 Control Panel Standard - Features for False Alarm Reduction
This product is UL/ULC listed under the following categories:
AMCX/AMCXC
Central Stations Alarm Units
APAW
Police-station-connected Alarm Units
DAYRC
Central Station Fire Alarm System Units
UTOU/UTOUC
Control Units and Accessories, Household System Type
NBSX/NBSXC
Household Burglar Alarm System Units
AMTB
Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 com-
pliance statement (Also Classified in accordance with SIA-CP-01 Standard) as proof of
compliance with the above mentioned standards. For further information on this product's
listings please also refer to the official listing guides published at the UL web site
(www.ul.com) under Certifications Section or ULC web site (www.ulc.ca) under Online
Directories.
UL/ULC Installations Required Programming Options
• All burglary-type zones shall be configured with SEOL or DEOL configuration (refer to
section [013], option 1 shall be OFF)
• Use at least one Smoke Detector for Fire Installations (refer to section [001], fire zone
shall be programmed as type 08 (hardwired) or 88 (wireless))
• The entry delay shall not exceed 60 seconds (refer to section [005])
• The exit delay shall not exceed 120 seconds (refer to section [005])
• The minimum Bell Time-out is 4 minutes (refer to section [005])
For ULC Residential Fire Installations the minimum Bell Time-out is 5 min.
For UL Home Health Care Installations the minimum Bell Time-out is 5 min.
For UL Commercial Burglary Installations minimum Bell Time-out is 15 min.
• Temporal Three Fire Signal shall be enabled (Section [013], option 8 shall be ON)
• Arm/Disarm Bell Squawk shall be enabled when using wireless key WS4939 (refer to
section [014], option 1 shall be ON)
• A code will be required for bypassing (Section [015], option 5 shall be ON)
• Trouble beeps shall be enabled (Section [023], option 7 shall be ON)
• AC trouble indication LED shall be enabled (refer to Keypad Programming, section
[075], options 5 and 6 shall be ON )
• DACT Communicator shall be enabled for Supervising Station Monitoring (refer to sec-
tion [380], option 1 shall be ON).
The DACT communicator for this product has no line security.
• Telephone Line Monitoring (TLM) shall be enabled (refer to section [015], option 7 shall
be ON)
The product shall be programmed to perform 5 (min.) to 10 (max.) attemptsfor com-
munication of an event to the supervising station. If unsuccessful, a Fail To Commu-
nicate (FTC) trouble is generated.
Test transmission cycle shall be set for monthly transmission (see Section [377])
For ULC Residential/Commercial installations set for daily test transmission
UL Central Station and Police Connect with Standard or Encrypted Line Security
Service
• The installation must use the T-Link TL250 or T-Link TL300 Internet/Intranet communi-
cator which communicates over LAN/WAN/Internet to the SG-System II or SG-System
II receivers.
• Polling time shall be 200 seconds and compromise detection time shall be 6 min.
• For Encrypted line security applications, the T-Link TL250 or TL300 shall have the
Encryption Key enabled (AES128 bit encryption algorithm is validated under NIST Cer-
tificate No. 109).
UL Local, Central Station and Police Connect with No Line Security Service
• The installation shall use a Bell which is UL Listed for Mercantile local alarms (i.e.
AMSECO MBL10B with model AB-12 bell housing.
• The digital communicator shall be enabled
• The control panel shall be in the attack resistant enclosure DSC Model CMC-1 or
PC4050CAR
UL Home Health Care Signaling Equipment
• There must be at least two keypads, one of either one of the compatible keypads models
PK5500, PK5501, PK5508, PK5516
• Each system shall be programmed to activate an audible Trouble signal within 90 sec-
onds upon loss of microprocessor memory
Appendix B: UL Listed Commercial and Residential Installations
ULC Central Station Fire and Burglary Monitoring Installations
• For installation requirements, levels of security, communication modules and configura-
tions (Refer to the ULC Installation Information Sheet, DSC #29002157)
• Use a CSA/cUL approved transformer (hardwired connections required for Fire Moni-
toring)
• All tamper circuits may be connected to the same zone
Programming
The notes in the programming sections describing the system configurations for UL/ULC
listed installations shall be implemented
Control of the Protected Premises
In order to have a UL certificated system the protected are is to be under the responsibility
of one ownership and management (i.e., one business under one name). This may be a
group of buildings attached or unattached with different addresses but under the responsi-
bility of someone having mutual interest. The person of the mutual interest is not the
alarm-installing company.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the person
operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and the local power supply must be protected in one of the follow-
ing ways:
• The control unit and audible alarm device must be in a protected area which is armed 24
hours a day.
• Each partition must arm the area protecting the control unit and the audible alarm device
power supply. This may require duplicate protection armed by each partition. Access to
this protected area, without causing and alarm, will require that all partitions be dis-
armed.
• In all cases described above, the protected area for the control unit must be programmed
as not-bypassable.
Casual Users
The installer should caution the user(s) not to give system information (e.g. codes, bypass
methods, etc.) to casual users (baby-sitters or service people). Only the One-Time Use
codes shall be given to casual users.
User Information
The installer should advise the users and note in the User's Manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
• Test system weekly
• The installer's code cannot arm or disarm the system
SIA False Alarm Reduction Installations
Minimum required system consists of one Control unit model PC1864 or PC1832 or
PC1616 and any one of the compatible listed keypads: PK5500, PK5501, PK5508,
PK5516, PKP-LCD, PKP-ICN. For a list of the defaults value programmed when the unit
is shipped from the factory and for any other programming information refer to Appendix
C: False Alarm Reduction.
The following optional subassembly modules also bear the SIA CP-01-2000 classification
and may be used if desired: PC5108 Zone Expander, PC5208 PGM Output Module,
PC5204 Auxiliary Power Supply and PC5400 Serial Output Module.
CAUTION
• For SIA FAR installations use only modules/devices that are listed on this page
• Fire Alarm Verification feature (Auto Verified Fire Zone type [29]) is not supported on
2-wire smoke detectors zones. This feature may be enabled for 4-wire smoke detectors
only . The fire alarm delay is 60s.
• Call Waiting Cancel (Section [382], Option 4) feature on a non-Call Waiting line will
prevent successful communication to the supervising station.
• All smoke detectors on the system must be tested annually by conducting the Installer
Walk Test. Prior to exiting the walk test mode, a sensor reset must be conducted on the
system, [*][7][2] to reset all latching 4-wire smoke detectors. Please refer to the smoke
detector installation instructions on how to correctly test the detectors.
NOTES
• Programming at installation may be subordinate to other UL requirements for the
intended application
• Cross zones have the ability to individually protect the intended area (e.g. motion detec-
tors which overlap)
• Cross zoning is not recommended for line security Installations nor is to be implemented
on exit/entry zones.
• There is a communication delay of 30 seconds in this control panel. It can be removed, or
it can be increased up to 45 seconds at the option of the end user by consulting with the
installer.
• Do not duplicate any reporting codes. This applies for all communication formats other
than SIA or CID sending automatic programmed reporting codes.
• The security system shall be installed with the sounding device activated and the com-
municator enabled for transmission using SIA or CID format.
57