Operation Lock (Press [Mode] For An Extended Time (2S)) - Mitsubishi Electric FR-F700 Series Instruction Manual

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Operation panel (FR-DU07)
3.2.3

Operation lock (Press [MODE] for an extended time (2s))

Operation using the setting dial and key of the operation panel can be made invalid to prevent parameter
change and unexpected start and stop.
· Set "10 or 11" in Pr. 161, then press
· When the setting dial and key operation is made invalid,
When the setting dial and key operation is invalid,
performed. (When the setting dial or key operation is not performed for 2s, the monitor display appears.)
· To make the setting dial and key operation valid again, press
POINT
Set "0" (extended mode parameter valid) in Pr.160 User group read selection.
Set "10 or 11" (key lock mode valid) in Pr.161 Frequency setting/key lock operation selection.
1.
Screen at powering on
The monitor display appears.
2.
Press
operation mode.
3.
Press
setting mode.
4.
Turn
5.
Press
"
"(initial value) appears.
6.
Turn
it to the setting value of "
7.
Press
8.
Press
Stop and reset with
REMARKS
Pr. 161 will not be displayed when simple mode (Pr. 160 User group read selection="9999") is selected. (Refer to page 50 )
30
for 2s to make the setting dial and key operation invalid.
Operation
to choose the PU
to choose the parameter
(Pr. 161) appears.
until
to read the currently set value.
counterclockwise to change
".
to set.
for 2s to show the key lock mode.
Functions valid even in the operation lock status
.
appears on the operation panel.
appears if the setting dial or key operation is
for 2s.
Display
PU indication is lit.
Flicker
Parameter setting complete!!
···
Press for 2s.
The parameter
number read
previously
appears.