Mitsubishi Electric FR-F700 Series Instruction Manual page 23

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Wiring
Terminal
Terminal
Symbol
Name
Analog current
CA
output
Analog voltage
AM
output
*1
Low indicates that the open collector output transistor is on (conducts).
High indicates that the transistor is off (does not conduct).
*2
Not output during inverter reset.
(3) Communication
Terminal
Terminal
Symbol
Name
PU
PU
connector
connector
Inverter
TXD+
transmission
TXD-
terminal
Inverter
RXD+
reception
RXD-
terminal
SG
Ground
(4) Control circuit terminal layout
Terminal screw size: M3.5
Tightening torque: 1.2N·m
(5) Wiring instructions
1)
Terminals 5, PC and SE are common to the I/O signals and isolated from each other. Do not ground.
2)
Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main
and power circuits (including the 200V relay sequence circuit).
3)
Use two or more parallel micro-signal contacts or twin
contacts to prevent a contact faults when using contact inputs
since the control circuit input signals are micro-currents.
4)
Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.
5)
Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp, etc.
6)
It is recommended to use the cables of 0.75mm
If the cable gauge used is 1.25mm
or the cables are run improperly, resulting in an operation panel contact fault.
7)
The wiring length should be 30m (98.43feet) maximum.
18
Description
Select one e.g. output frequency
from monitor items.
*2
The output signal is proportional to
the magnitude of the corresponding
monitoring item.
Description
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485(RS-485)
. Transmission format
: Multidrop
. Communication speed : 4800 to 38400bps
. Overall length
: 500m (1640.42feet)
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard
: EIA-485(RS-485)
Transmission format
: Multidrop link
Communication speed : 300 to 38400bps
Overall length
: 500m (1640.42feet)
A1
B1
RL
RM
RH
SE
RUN
SU
2
gauge for connection to the control circuit terminals.
2
or more, the front cover may be lifted when there are many cables running
Output item:
Output frequency
(initial setting)
C1
A2
B2
C2 10E 10
RT
AU
STOP
MRS
RES
IPF
OL
FU
SD
SD
STF
Micro signal contacts
Rated
Refer to
Specifications
Load impedance
Instruction
200Ω to 450Ω
Manual
Output signal 0 to
(applied)
20mADC
Output signal 0
to 10VDC
Instruction
Permissible load
current 1mA
Manual
(load impedance
(applied).
10kΩ or more)
Resolution 8 bit
Rated
Refer to
Specifications
2
5
4
SD
CA
AM
1
STR
JOG
CS
PC
Twin contacts
23
24