Mitsubishi Electric FR-F700 Series Instruction Manual page 78

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Operation Panel
Indication
Name
Communication error (inverter)
This function stops the inverter output when communication error occurs consecutively for more than
permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication number of retries
Description
during RS-485 communication from the RS-485 terminals. This function also stops the inverter output if
communication is broken for the period of time set in Pr. 336 RS-485 communication check time interval.
Check point
Check the RS-485 terminal wiring.
Corrective action
Perform wiring of the RS-485 terminals properly.
Operation Panel
Indication
Name
Analog input error
Appears when 30mA or more is input or a voltage (7.5V or more) is input with the terminal 2/4 set
Description
to current input.
Check the setting of Pr. 73 Analog input selection and Pr. 267 Terminal 4 input selection. (Refer to the
Check point
Instruction Manual (applied).)
Either give a frequency command by current input or set Pr. 73 Analog input selection or Pr. 267
Corrective action
Terminal 4 input selection to voltage input. (Refer to the Instruction Manual (applied).)
Operation Panel
Indication
Name
Internal circuit error
Description
Appears when an internal circuit error occurred.
Corrective action
Please contact your sales representative.
CAUTION
• If protective functions of E.ILF, E.PTC, E.PE2, E.CDO, E.IOH, E.SER, E.AIE, E.13 are activated when using the FR-PU04,
"Fault 14" appears.
Also when the alarm history is checked on the FR-PU04, the display is "E.14".
• If alarms other than the above appear, contact your sales representative.
E.SER
E.AIE
E.13
Causes and corrective actions
FR-PU04
Fault 14
FR-PU04
Fault 14
FR-PU07
Fault 14
5
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents