Communications Connection Terminal - YASKAWA Varispeed G7 Instruction Manual

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7:
Table of Contents

Advertisement

Communications Connection Terminal

MEMOBUS communications use the following terminals: S+, S-, R+, and R-. Set the terminating resistance
by turning ON pin 1 of switch S1 for the last Inverter only, as seen from the PLC.
S+
S-
RS-422A
or RS-485
R+
R-
Terminating resistance (1/2 W, 110 Ohms)
1. Separate the communication cables from the main circuit cables and other wiring and power cables.
2. Use shielded cables for the communication cables, connect the shield cover to the Inverter earth terminal,
and arrange the terminals so that the other end is not connected to prevent operating errors due to noise.
3. When using RS-485 communications, connect S+ to R+, and S- to R-, on the Inverter exterior.
IMPORTANT
Procedure for Communicating with the PLC
Use the following procedure to perform communications with the PLC.
1. Turn OFF the power supply turned and connect the communication cable between the PLC and the
Inverter.
2. Turn ON the power supply.
3. Set the required communications constants (H5-01 to H5-07) using the Digital Operator.
4. Turn OFF the power supply, and check that the Digital Operator display has completely disappeared.
5. Turn ON the power supply once again.
6. Perform communications with the PLC.
Set the timer on the master to monitor response time from the slave. Set the master so that if the slave does
not respond to the master within the set time, the same command message will be sent from the master
again.
INFO
+
-
S1
O
F
F
Switch
1
Fig 6.59 Communications Connection Terminal
R+
R
OFF
1
2
S+
S
Individual Functions
Terminating
ON
resistance
93