Options; Performing Speed Control With Pg - YASKAWA Varispeed G7 Instruction Manual

General purpose inverter (advanced vector control)
Hide thumbs Also See for Varispeed G7:
Table of Contents

Advertisement

Options

This section explains the Inverter option functions.

Performing Speed Control with PG

This section explains functions with V/f control with PG.
Related Constants
Con-
stant
Number
F1-01
F1-02
F1-03
F1-04
F1-05
-158
6
Name
Description
Display
PG constant
Sets the number of PG (pulse gen-
erator or encoder) pulses.
Sets the number of pulses per
PG Pulses/Rev
motor revolution.
Operation
Sets the PG disconnection stop-
selection at PG
ping method.
open circuit
0: Ramp to stop (Deceleration
(PGO)
stop using Deceleration Time
1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop
using the deceleration time in
PG Fdbk Loss
C1-09.)
Sel
3: Continue operation (To protect
the motor or machinery, do not
normally make this setting.)
Operation
Sets the stopping method when an
selection at
overspeed (OS) fault occurs.
overspeed (OS)
0: Ramp to stop (Deceleration
stop using Deceleration Time
1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop
PG Overspeed
using the deceleration time in
Sel
C1-09.)
3: Continue operation (To protect
the motor or machinery, do not
normally make this setting.)
Operation
Sets the stopping method when a
selection at
speed deviation (DEV) fault
deviation
occurs.
0: Ramp to stop (Deceleration
stop using Deceleration Time
1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop
PG Deviation
using the deceleration time in
Sel
C1-09.)
3: Continue operation (DEV is
displayed and operation
continued.)
PG rotation
0: Phase A leads with Forward
Run Command. (Phase B
leads with Reverse Run Com-
mand.)
1: Phase B leads with Forward
PG Rotation Sel
Run Command. (Phase A
leads with Reverse Run Com-
mand.)
Control Methods
Change
Setting
Factory
during
V/f
Range
Setting
Opera-
V/f
with
tion
PG
0 to
600
No
No
Q
60000
0 to 3
1
No
No
A
0 to 3
1
No
No
A
0 to 3
3
No
No
A
0 or 1
0
No
No
A
MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
No
Q
No
380H
No
A
No
381H
No
A
A
382H
No
A
A
383H
No
A
No
384H

Hide quick links: