Flue Terminal Positioning - Potterton Paramount two Installation, Operation & Maintenance Manual

Wall hung condensing boiler 30 – 115kw
Table of Contents

Advertisement

5.6

Flue terminal positioning

Fig. 4:
Location
A
Below an opening
B
Above an opening
C
Horizontally to an opening
D
Below Gutters, soil pipes or drain pipes
PARAMOUNT two 30 - 115 kW
– per 45° elbow = 0.50 m
– per 30° elbow = 0.35 m
– per 15° elbow = 0.20 m
Existing Chimneys
If a chimney, which was previously used for oil or solid fuel fur-
naces, is used for installing a concentric flue gas pipe, it is neces-
sary for the chimney to be thoroughly cleaned.
Installation
The flue gas pipe must be installed with a slope from the PARA-
MOUNT two so that condensate from the flue gas pipe can drain
into the central condensate sump in the PARAMOUNT two.
The minimum slope is as follows:
– Horizontal flue pipe: min 3°
Height above Roof
Refer to relevant British Standards and Code of Practice.
Minimum clearances for concentric room sealed flue terminals (for
conventional flue systems please refer to the relevant BS). The ter-
minal shall be positioned so it will not cause a hazard to health of
persons who may be nearby or a nuisance to other person beyond
the cartilage (fig. 4).
PARAMOUNT two 30/40/60
Installation
PARAMOUNT two 80/95/
115
300
600
300
600
300
600
75
150
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents