Sensor Value Tables - Potterton Paramount two Installation, Operation & Maintenance Manual

Wall hung condensing boiler 30 – 115kw
Table of Contents

Advertisement

3.5

Sensor value tables

PARAMOUNT two 30 - 115 kW
Table 4: Resistance values for outside temperature sensor ATF
Temperature [°C]
-20
-15
-10
-5
0
5
10
15
20
25
30
Table 5: Resistance values for flow sensor, DHW sensor, return sensor,
sensor B4
Temperature [°C]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
Ω
Resistance [
]
8194
6256
4825
3758
2954
2342
1872
1508
1224
1000
823
Ω
Resistance [
]
32555
25339
19873
15699
12488
10000
8059
6535
5330
4372
3605
2989
2490
2084
1753
1481
1256
1070
915
786
677
Technical Data