Fan Control Module Switch (Dri3030Ten Model Only); Installation; Venting Installation - Superior DRI3030TEN Installation And Operation Manual

Direct-vent fireplace insert
Hide thumbs Also See for DRI3030TEN:
Table of Contents

Advertisement

FAN CONTROL MODULE SWITCH
DRI3030TEN-33 and DRI3030TEN-40 Models Only
Before installation, verify the power switch on the Fan Control Module is
in the ON position (as shown in Figure 6).
Fan Control
Module (FCM)
Figure 6
"ON" Position
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

INSTALLATION

Venting Installation

Your IHP appliance must be vented to the outside in accordance with the
current edition of the National Fuel Gas Code ANSI-Z223.1 (In Canada, the
current CAN/CGA B149.1 installation code). The insert must not be con-
nected to a chimney flue serving a separate solid fuel burning appliance.
This appliance requires a 3" diameter listed flex liner. The vent should
terminate with a listed direct-vent termination cap. The chimney should be
sealed around the cap to prevent air and rain from entering the chimney.
Adhere to the vent manufacturer's instructions for installation and vent
termination. These appliances are approved for use with the following
vent kits.
Amerivent -
Flex Liner 3" X 35' - #3AFL-35
Adaptor w/ Flashing - #4DCAT33
Termination Cap - #4DVC
Selkirk -
Flex Liner 3" X 35' - #AF35-03
Flex Liner 3" X 25' - #AF25-03
Flex Liner 3" X 15' - #AF15-03
Adaptor w/ Flashing - #4DT-CTB
Termination Cap - #4DT-VT
Simpson Dura Vent -
Flex Liner 3" X 35' - #3DFA-35
Adaptor w/ Flashing - #46DVA-GK
Termination Cap - #46DVA-VCH With #460 DVA-VWG
Termination Cap - #46DVA-VC
Co-Linear Kit w/ 3" X 35' Flex Liner (Intake and Exhaust), Adaptor, Flashing
and Termination Cap - #46DVA-CL33
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dri2530ten

Table of Contents