Installation - Superior TF18NE Installation And Operation Instructions Manual

Superior unvented (vent-free) gas log heater
Table of Contents

Advertisement

AIR FOR COMBUSTION AND VENTILATION
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Ventilation
Grills Into
Adjoining
Or
Room,
Remove
Option 1
Door into
Adjoining
Room,
Option
3
Figure 2 - Ventilation Air from Inside Building
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri-
mary heat source. If you have a
central heating system, you may
run system's circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
8
12"
Ventilation Grills
Into Adjoining Room,
Option 2
12"

INSTALLATION

www.SuperiorFireplaces.US.com
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling
and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings
for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Outlet
Air
Inlet
Air
Figure 3 - Ventilation Air from Outdoors
WARNING: A qualified ser-
vice person must install heater.
Follow all local codes.
WARNING: Any outside air
ducts and/or ash dumps in the
fireplace shall be permanently
closed at time of appliance in-
stallation.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on floor or wall of fire-
place. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney flue damper.
Ventilated
Outlet
Attic
Air
Ventilated
Inlet Air
Crawl Space
To Attic
To
Crawl
Space
126818-01A