Min. Framing Dims. - Rear Vent Configuration; Minimum Framing Dimensions - Rear Vent Configuration - Travis Industries 864 TRV GreenSmart Installation Manual

Built-in direct vent fireplace
Hide thumbs Also See for 864 TRV GreenSmart:
Table of Contents

Advertisement

12

Minimum Framing Dimensions - Rear Vent Configuration

HINT: place the fireplace so the center
line is at least 5" (127mm) from both
vertical framing members at the rear (this
allows the vent to pass through the
framing without modfications)
Route the
electrical line to
a position to the
left rear of the
fireplace.
Minimum enclosure height = 38-1/2" (978mm)
© Travis Industries
Installation
38-1/2"
978mm
41-1/4"
1048mm
(for qualified installers only)
Included Firestop (required)
Part # 93006094
38"
965mm
25-3/4"
654mm
20"
508mm
4090227
Vent Clearances 8" (203mm) dia. Vent:
1" (25mm) to the sides, 1" (25mm)
below, and 3" (76mm) above the vent to
combustibles.
Center of Rear Vent
30-3/4"
781mm
The on/off switch/thermostat wire (if
used) should be routed to a location
near the right front of the fireplace.
100-01220_000