Short Cycle Start Up Protection; Frequently Asked Questions - Z-Wave ZTS-100 User Manual

Z-thermostat
Table of Contents

Advertisement

Short Cycle Start Up Protection

To protect the compressor / Heat pump, those outputs forced off until 3minutes count down finished.
Those outputs can be activated according to the room temperature after 3 minutes.
System
Non Heat pump system
Heat pump system

Frequently Asked Questions

Q Why won't my ZTS-100 work with the Z-Wave devices I purchased from another country?
A Due to different countries regulations Z-Wave products from different regions are set to different
frequencies. Before purchasing new devices make sure you have checked to see that the device is
compatible in your region.
Q Do I need an electrician to install ZTS-100 in my house?
A It is recommended to install this product by a qualified technician.
Q How do I know which product is compatible to my ZTS-100?
A ZTS-100 should work with any Z-Wave controller or gateway that has control capability for
"Thermostat" devices. You can check either the specifications in the manual of your ZTS-100 or
also check online at www.remotec.com.hk for a full list of products that can be used with your
ZTS-100. All Z-Wave products also come with the Z-Wave logo.
Q Can I use 2 or more ZTS-100 in my house? What is the max. units if yes?
A Yes and it is very depends on the capability of gateway / controller. For example, gateway can
supports up to 8, 16 or 32 ZTS-100 in a network.
Q Where can I keep up to date with the latest Z-Wave products for my house?
A You can keep up to date by visiting the www.remotec.com.hk website where we will have
information and ideas for using Z-Wave technology.
Q What are the operation for Swing and Differential set point?
A Below are the detail explanations.
HEAT mode: thermostat controls the temperature according to the following diagram
Output
nd
2
Turn on
1
Off
Example for Heating: (Set point = 70 °F, Swing = 1 °F, Differential = 2 °F)
=> 1st stage heater turns on when room temp is 69 °F and off at 71 °F.
=> 2nd stage heater turns on when room temp is 67 °F and off at 70 °F.
Output
Compressor
1st stage heat and compressor
Set point
nd
2
st
Turn on
Diff
Swing
Swing
Turn off
st
1
Turn off
31
Heat
Temperature
SD= switch differential