Troubleshooting
Checking and acknowledging faults
Fault code
Const.
in the dis-
play
F7
X
F8
X
F9
X
FA
X
Fd
X
82
Weat-
System
h.
character-
comp.
istics
X
Burner
blocked
X
Burner in
fault state
X
Burner in
fault state
X
Burner in
fault state
X
Burner
blocked
(cont.)
Cause
Remedy
Differential pres-
Check the dif-
sure sensor faulty
ferential pres-
sure sensor
and lead.
Fuel valve closes
Check gas
too late
combination
valve. Check
both control
paths.
Press E.
Fan speed too low
Check the
at burner start
fan, check the
fan cables
and supply,
check the fan
control.
Press E.
.
Fan speed too high
Check the
at burner start
fan, check the
fan cables,
check the fan
control.
Press E.
Burner control unit
Check the
fault
ignition elec-
trodes and
leads. Check
whether a
strong inter-
ference
(EMC) field
exists near
the equip-
ment.
Press E.
If the fault is
not removed,
replace the
control unit.