Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
7F:1
*
1
Detached house
80:1
With 5 seconds time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
81:1
Automatic change
between summer and
winter
88 :0
Temperature display in
°Celsius
8A:175
Do not adjust
90:128
Time constant for calcu-
lating adjusted outside
temperature 21.3 h
*1
Only for weather-compensated control unit.
50
Coding
Possible change
change
Address:
value
7F:0
Multi-occupancy house
Separate adjustment for
holiday program and time
program for DHW load-
ing, as option
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
changeover
81:2
The application of the
radio clock module will be
recognised automatically
81:3
Accept time via LON
88 :1
Temperature display in
Fahrenheit
90:0
Quick (low values) or
to
slow (high values) match-
90:199
ing of flow temperature
subject to set value if the
outside temperature
changes;
1 step = 10 min.