Further details regarding the individual steps
Checking and replacing the magnesium anode (if required)
Check the magnesium anode. We
recommend you change the magne-
sium anode if it has been reduced
down to 10 to 15mm Ø.
Taking the DHW cylinder back into use
Initial start-up, inspection, maintenance
(cont.)
5. Remove hard deposits that cannot
be removed by a high pressure
cleaner, with a chemical cleaning
agent.
!
Important information
Never use hydrochloric
cleaning agents.
6. Thoroughly flush the DHW cylinder
after cleaning.
1. Reconnect the DHW cylinder to the
pipework.
2. Insert new gasket A underneath
the flange lid B.
3. Fit flange lid B and tighten the
screws with a maximum torque of
25 Nm.
4. Push earth cable C onto connect-
ing tab D.
5. Fill the DHW cylinder with potable
water.