Viessmann VITODENS 333 Service Instructions Manual page 52

Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for VITODENS 333:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
9C:20
*
1
Monitoring LON users
When there is no
response from a user,
values defaulted inside
the control unit continue
to be used for a further
20 minutes. Only then
will a fault message be
triggered.
9F:8
*
1
Differential tempera-
ture 8 K; only in con-
junction with a mixer
circuit
Boiler circuit, mixer circuit
A0:0
*
1
Without remote con-
trol
*1
Only for weather-compensated control unit.
52
Coding
Possible change
change
Address:
value
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 minutes
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)