Checking and acknowledging faults
Constant temperature control units
Fault code
Const.
in the dis-
play
0F
X
10
X
18
X
20
X
28
X
Note
The fault can be acknowledged
with d. The fault message in the dis-
play will be hidden, but the red fault
indicator U continues to flash. A new
fault message will be displayed if an
acknowledged fault is not removed by
the following morning.
Calling up acknowledged fault mes-
sages
Press d for approx. 2 seconds;
select the acknowledged fault with a
or b.
Weat-
System
h.
character-
comp.
istics
X
Control
mode
X
Controls
according
to 0 °C out-
side tem-
perature
X
X
Controls
without
flow tem-
perature
sensor
(low loss
header)
X
Troubleshooting
(cont.)
Cause
Remedy
Maintenance
Carry out
maintenance.
Set code 24:0
after mainte-
nance.
Outside tempera-
Check the
ture sensor shorted
outside tem-
out
perature sen-
sor (see
page 84)
Outside tempera-
ture sensor lead
break
System flow tem-
Check the
perature sensor
low loss
shorted out
header sen-
sor (see
page 85).
System flow tem-
perature sensor
lead break
75