Calibration Of The Am Terminal - Mitsubishi Electric FR-PU07 Instruction Manual

Hide thumbs Also See for FR-PU07:
Table of Contents

Advertisement

7
Press
.
Calibration is complete.
8
Press
to return to the
main monitor screen.
REMARKS
When FR-PU07BB is used in the battery mode (the
inverter power is OFF), this parameter cannot be set
(calibrated).
Calibration of the Meter (Frequency Meter)
2.5.2
900 FM Tune
Completed
<MONITOR>
Pr. 901 AM terminal calibration
Pr. 158 AM terminal function selection
Pr. 55 Frequency monitoring reference
READ:List
Pr. 56 Current monitoring reference
60.00
Hz
STF FWD PU
This section provides a way to calibrate the meter
connected to terminal AM using the parameter unit.
(1) Calibration procedure 1
1
2
3

Calibration of the AM terminal

Parameter
(Example: To calibrate the meter at the
running frequency of 60Hz)
Press
.
The frequency setting screen
appears, and operation mode
changes to PU operation mode.
Press
.
The parameter unit is in the
parameter setting mode.
Enter
and
press
.
The preset frequency is
displayed.
Freq Set
SET
0.00Hz
0~400Hz
2
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
901 AM Tune
Run Inverter
0.00Hz
PU
43