Calibration of the Meter (Frequency Meter)

2.5
Calibration of the Meter (Frequency Meter)
The functions vary with the inverter. (Refer to the inverter instruction manual for details of the parameters.)
2.5.1

Calibration of the FM terminal

Parameter
Pr. 900 FM terminal calibration
Pr. 54 FM terminal function selection
Pr. 55 Frequency monitoring reference
This section provides the way to calibrate the full-
scale of meter connected to terminal FM using the
parameter unit.
• Calibrating the meter at the running frequency of
60Hz
1
Press
.
The frequency setting screen
appears, and operation mode
changes to PU operation mode.
2
Press
.
The parameter unit is in the
parameter setting mode.
42
3
4
5
Freq Set
SET
0.00Hz
0~400Hz
6
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
Enter
and
press
.
The preset frequency is
displayed.
Enter
and press
.
60Hz is set.
Press
.
Forward rotation is performed
at 60Hz. You need not
connect the motor.
Using
/
, adjust
the meter pointer to a
predetermined position.
The meter pointer moves. (It
takes a long time before the
pointer moves.)
900 FM Tune
Run Inverter
0.00Hz
PU
900 FM Tune
Run Inverter
60Hz
PU
900 FM Tune
MntrF
60.00Hz
<WRITE>PU