Indoor-Fan Motor Performance; Performance Data - Carrier 50TFQ004 Product Data

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

Performance data (cont)
UNIT
INDOOR-FAN
50TFQ
MOTOR
Standard
004
Alternate
High Static
Standard
005
Alternate
High Static
Standard
006
Alternate
High Static
Standard
007
High Static
Standard,
Alternate
008
High Static
Standard
009
High Static
Standard
012
Alternate
High Static
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horse-
power range of the motors can be utilized with confidence. Using your fan motors
up to the horsepower ratings shown in this table will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
†Single-phase/three-phase.
52

INDOOR-FAN MOTOR PERFORMANCE

UNIT
MAXIMUM ACCEPTABLE
VOLTAGE
CONTINUOUS BHP*
208/230
460
0.34
575
208/230
460
1.00
575
208/230
460
2.40
575
208/230
460
0.75
575
208/230
460
1.00
575
208/230
460
2.40
575
208/230
460
1.20
575
208/230
460
1.30/2.40†
575
208/230
460
2.90
575
208/230
460
2.40
575
208/230
460
2.90
575
208/230
460
2.40
575
208/230
460
3.70
575
208/230
460
2.40
575
208/230
460
3.70
575
208/230
460
2.40
575
208/230
460
2.90
575
208/230
460
5.25
575
MAXIMUM ACCEPTABLE
OPERATING WATTS
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
MAXIMUM
AMP DRAW
3.3
440
1.8
1.8
5.1
1000
2.2
2.2
6.1
2120
2.7
2.7
3.1
850
1.9
1.9
5.1
1000
2.2
2.2
6.1
2120
2.7
2.7
6.2
1340
3.4
3.4
9.2/6.1†
2120
2.7
2.7
6.1
2562
2.7
2.7
6.1
2120
2.7
2.7
7.9
2562
3.6
3.6
6.1
2120
2.7
2.7
11.1
3313
5.0
5.0
6.1
2120
2.7
2.7
11.1
3313
5.0
5.0
6.1
2120
2.7
2.7
7.9
2615
3.6
3.6
15.0
4400
7.4
7.4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents