Carrier 50TFQ004 Product Data page 41

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
1500
789
0.40
1600
826
0.46
1700
865
0.54
1800
905
0.62
1900
945
0.72
2000
984
0.82
2100
1024
0.93
2200
1064
1.05
2300
1104
1.18
2400
1145
1.32
2500
1186
1.48
50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
1500
1221
1.17
1600
1252
1.27
1700
1278
1.37
1800
1303
1.48
1900
1330
1.59
1362
1.73
2000
2100
1393
1.87
2200
1423
2.02
2300
1454
2.18
2400
1485
2.36
2500
1518
2.55
LEGEND
— Brake Horsepower Input to Fan
Bhp
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils. See
page 49 for accessory/FIOP static pressure information.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
0.4
Watts
Rpm
Bhp
Watts
420
896
0.53
557
483
931
0.61
641
567
966
0.69
725
661
1002
0.78
820
757
1037
0.88
925
862
1072
0.98
1030
977
1108
1.10
1156
1103
1145
1.22
1282
1240
1183
1.36
1429
1387
1222
1.45
1524
1555
1262
1.68
1765
1.4
Watts
Rpm
Bhp
Watts
1229
1256
1.30
1366
1334
1311
1.45
1524
1439
1345
1.57
1650
1555
1371
1.69
1776
1671
1396
1.80
1902
1818
1422
1.94
2038
1965
1452
2.08
2185
2122
1483
2.24
2354
2291
1515
2.41
2532
2480
1544
2.59
2721
2679
1574
2.78
2905
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
990
0.67
704
1020
0.75
788
1051
0.84
883
1084
0.93
977
1119
1.04
1093
1154
1.16
1219
1192
1.29
1355
1225
1.43
1503
1260
1.57
1650
1296
1.73
1818
1331
1.89
1986
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
1283
1.32
1387
1340
1.58
1660
1397
1.76
1849
1433
1.90
1996
1460
2.03
2133
1485
2.16
2270
1510
2.31
2427
1538
2.46
2585
1571
2.64
2758
1604
2.84
2947
1633
3.03
3134
4. Maximum continuous bhp is 2.9 and the maximum continuous watts
are 2562. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Indoor-Fan Motor Performance table
on page 52 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.8
Rpm
Bhp
Watts
Rpm
1072
0.83
872
1153
1101
0.91
956
1178
1133
1.01
1061
1205
1163
1.10
1156
1235
1194
1.21
1271
1266
1226
1.33
1397
1297
1259
1.47
1545
1327
1294
1.62
1702
1359
1330
1.78
1870
1392
1365
1.94
2038
1426
1400
2.12
2227
1461
1.8
Rpm
Bhp
Watts
Rpm
1303
1.22
1282
1345
1330
1.61
1692
1373
1424
1.89
1986
1470
1480
2.09
2196
1528
1517
2.25
2364
1566
1544
2.40
2522
1594
1570
2.55
2674
1620
1594
2.71
2821
1645
1623
2.88
2976
1675
1657
3.07
3152
1710
1692
3.28
3345
1746
1.0
Bhp
Watts
1.00
1051
1.09
1145
1.18
1240
1.29
1355
1.40
1471
1.53
1608
1.66
1744
1.80
1902
1.97
2070
2.15
2259
2.34
2459
2.0
Bhp
Watts
1.34
1390
1.77
1834
2.08
2153
2.30
2381
2.47
2563
2.64
2734
2.80
2905
2.98
3087
3.17
3280
3.38
3497
3.61
3736
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents