Carrier 50TFQ004 Product Data page 46

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

Performance data (cont)
50TFQ009 (8
1
/
TONS) — STANDARD MOTOR (BELT DRIVE)*
2
Airflow
0.2
(Cfm)
Rpm
Bhp
2550
501
0.57
2660
507
0.59
2700
520
0.65
2800
533
0.71
2900
546
0.77
3000
559
0.83
3100
572
0.90
3200
585
0.96
3300
598
1.03
3400
610
1.10
3500
623
1.17
3600
636
1.25
3700
649
1.33
3750
655
1.37
3800
661
1.41
3900
674
1.49
4000
687
1.57
4100
699
1.60
4200
712
1.75
4250
719
1.80
50TFQ009 (8
1
/
TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)
2
Airflow
1.2
(Cfm)
Rpm
Bhp
2550
836
1.83
2660
839
1.87
2700
846
1.95
855
2.04
2800
2900
863
2.13
3000
872
2.22
3100
882
2.33
3200
892
2.45
3300
902
2.57
3400
912
2.69
921
2.82
3500
3600
930
2.95
3700
940
3.07
3750
945
3.14
3800
949
3.20
3900
959
3.33
4000
4100
4200
4250
LEGEND
— Brake Horsepower Input to Fan
Bhp
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
46
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
0.4
Watts
Rpm
Bhp
Watts
577
587
0.79
747
592
592
0.82
771
638
604
0.89
827
684
615
0.95
875
731
626
1.02
932
779
637
1.09
989
835
648
1.17
1056
883
660
1.24
1114
940
671
1.32
1182
998
682
1.41
1258
1056
694
1.50
1335
1123
707
1.60
1422
1190
720
1.71
1517
1224
727
1.77
1569
1258
733
1.82
1613
746
1.93
1709
1327
1396
759
2.05
1814
1473
772
2.17
1919
1552
785
2.30
2032
1595
792
2.37
2093
1.4
Watts
Rpm
Bhp
Watts
1621
887
2.13
1884
1656
891
2.17
1919
1726
898
2.26
1997
1805
906
2.35
2076
1884
913
2.44
2154
1962
921
2.54
2240
2058
930
2.65
2335
2162
939
2.76
2428
2266
948
2.88
2529
2369
958
3.01
2637
2479
968
3.15
2751
2587
978
3.29
2862
2686
2743
2781
2894
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
659
1.05
956
663
1.08
981
672
1.14
1031
683
1.20
1081
693
1.27
1140
704
1.35
1207
715
1.43
1275
727
1.52
1353
739
1.62
1439
750
1.72
1526
761
1.82
1613
772
1.93
1709
783
2.03
1796
789
2.09
1849
795
2.15
1901
806
2.26
1997
817
2.38
2102
828
2.50
2206
840
2.64
2326
846
2.71
2386
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
931
2.45
2162
936
2.49
2197
946
2.58
2275
954
2.67
2352
961
2.77
2436
969
2.88
2529
976
2.99
2620
984
3.10
2710
993
3.21
2799
1002
3.34
2902
3. Maximum usable watts input is 2120 and maximum continuous bhp
is 2.40. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. For additional information on motor perfor-
mance, refer to Indoor-Fan Motor Performance table on page 52.
4. Values include losses for filters, unit casing, and wet coils. See
page 49 for accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.8
Rpm
Bhp
Watts
Rpm
722
1.29
1156
780
727
1.32
1182
784
737
1.40
1250
793
747
1.49
1327
802
756
1.57
1396
813
765
1.66
1473
823
775
1.74
1543
832
785
1.83
1321
841
795
1.91
1691
851
806
2.01
1779
860
817
2.11
1866
870
828
2.23
1971
880
840
2.35
2076
890
846
2.42
2136
896
852
2.48
2188
901
863
2.61
2300
912
874
2.75
2420
923
885
2.88
2529
935
897
3.03
2653
947
903
3.10
2710
1.8
Rpm
Bhp
Watts
Rpm
964
2.77
2436
986
973
2.82
2479
999
987
2.91
2554
1019
997
3.01
2637
1034
1006
3.12
2727
1014
3.22
2807
1021
3.34
2902
1.0
Bhp
Watts
1.55
1378
1.58
1404
1.66
1473
1.75
1552
1.84
1630
1.94
1718
2.05
1814
2.15
1901
2.26
1997
2.36
2084
2.47
2180
2.57
2266
2.69
2369
2.75
2420
2.80
2462
2.93
2571
3.08
2694
3.23
2815
3.39
2940
2.0
Bhp
Watts
3.11
2718
3.16
2759
3.26
2839
3.36
2917

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents