Carrier 50TFQ004 Product Data page 30

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

Performance data (cont)
50TFQ007 (6 TONS)* — STANDARD MOTOR (BELT DRIVE)
Airflow
0.1
(Cfm)
Rpm
Bhp
1800
852
0.55
1900
894
0.64
2000
936
0.74
2100
978
0.85
2200
1021
0.97
2300
1064
1.10
2400
1107
1.24
2500
1150
1.39
2600
1193
1.56
2700
1237
1.74
2800
1280
1.94
2900
1324
2.15
3000
1368
2.37
50TFQ007 (6 TONS)* — STANDARD MOTOR (BELT DRIVE) (cont)
Airflow
1.0
(Cfm)
Rpm
Bhp
1800
1235
1.29
1900
1266
1.40
2000
1297
1.53
1327
1.66
2100
2200
1359
1.81
2300
1392
1.97
2400
1426
2.15
2500
1461
2.34
2600
1497
2.54
2700
1532
2.75
2800
2900
3000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
30
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
0.2
Watts
Rpm
Bhp
Watts
562
905
0.62
615
630
945
0.72
692
708
984
0.82
771
795
1024
0.93
859
891
1064
1.05
956
998
1104
1.18
1064
1114
1145
1.32
1182
1241
1186
1.48
1318
1387
1228
1.65
1465
1543
1269
1.83
1621
1718
1311
2.03
1796
1901
1354
2.24
1980
2093
1396
2.46
2171
External Static Pressure (in. wg)
1.2
Watts
Rpm
Bhp
Watts
1156
1303
1.48
1318
1250
1330
1.59
1413
1361
1362
1.73
1534
1473
1393
1.87
1656
1604
1423
2.02
1779
1744
1454
2.18
1927
1901
1485
2.36
2084
2067
1518
2.55
2249
2240
1552
2.76
2428
2420
External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
1002
0.78
739
1037
0.88
818
1072
0.98
899
1108
1.10
998
1145
1.22
1097
1183
1.36
1216
1222
1.52
1353
1262
1.68
1491
1301
1.86
1648
1341
2.05
1814
1381
2.25
1989
1420
2.47
2180
1460
2.69
2369
1.4
Rpm
Bhp
Watts
1371
1.69
1499
1396
1.81
1604
1422
1.94
1718
1452
2.08
1840
1483
2.24
1980
1515
2.41
2128
1544
2.59
2283
1575
2.78
2445
3. Maximum usable watts input is 2120 and maximum continuous
bhp is 2.40. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. For additional information on motor
performance, refer to Indoor-Fan Motor Performance table on
page 52.
4. Values include losses for filters, unit casing, and wet coils. See
page 49 for accessory/FIOP static pressure information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.6
Rpm
Bhp
Watts
Rpm
1084
0.93
859
1163
1119
1.04
948
1194
1154
1.16
1047
1226
1190
1.29
1156
1259
1225
1.43
1275
1294
1260
1.57
1396
1330
1296
1.73
1534
1365
1331
1.89
1674
1400
1367
2.07
1831
1435
1404
2.26
1997
1471
1442
2.47
2180
1506
1481
2.69
2369
1542
1521
2.93
2571
1.6
Rpm
Bhp
Watts
1433
1.90
1638
1460
2.03
1796
1485
2.16
1910
1510
2.31
2041
1538
2.46
2171
1569
2.64
2326
1601
2.84
2459
0.8
Bhp
Watts
1.10
998
1.21
1089
1.33
1190
1.47
1310
1.62
1439
1.78
1578
1.94
1718
2.12
1875
2.31
2041
2.51
2214
2.72
2394
2.94
2579