Carrier 50TFQ004 Product Data page 31

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

50TFQ007 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
1800
978
0.66
1900
1023
0.78
2000
1068
0.90
2100
1115
1.00
2200
1159
1.15
2300
1202
1.29
2400
1237
1.41
2500
1272
1.53
1320
1.68
2600
2700
1361
1.82
2800
1402
1.95
2900
1446
2.16
3000
1489
2.36
50TFQ007 (6 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
0.2
(Cfm)
Rpm
Bhp
1800
1395
1.46
1900
1430
1.58
2000
1459
1.67
2100
1489
1.80
2200
1528
1.95
2300
1561
2.13
1584
2.28
2400
2500
1633
2.53
2600
1675
2.77
2700
1775
3.45
2800
2900
3000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils. See
page 49 for accessory/FIOP static pressure information.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
0.4
Watts
Rpm
Bhp
Watts
700
1063
0.82
771
779
1097
0.91
843
867
1132
1.01
924
998
1180
1.17
1056
1081
1214
1.28
1148
1140
1248
1.38
1233
1224
1292
1.55
1378
1335
1335
1.71
1517
1482
1368
1.81
1604
1595
1400
1.91
1691
1639
1439
2.08
1840
1814
1477
2.16
1989
2032
1529
2.52
2223
0.4
Watts
Rpm
Bhp
Watts
1301
1475
1.56
1387
1404
1504
1.69
1499
1482
1532
1.82
1613
1595
1567
1.99
1761
1726
1603
2.17
1919
1884
1637
2.35
2076
2015
1671
2.55
2249
2232
1698
2.72
2405
2436
1768
3.26
2964
3141
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
1147
0.97
891
1175
1.11
1006
1218
1.23
1106
1261
1.35
1207
1310
1.52
1353
1358
1.69
1499
1392
1.81
1604
1427
1.94
1718
1458
2.06
1823
1490
2.19
1936
1543
2.43
2145
1585
2.65
2335
1598
2.73
2444
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
1542
1.71
1517
1556
1.82
1613
1588
1.97
1744
1626
2.16
1910
1666
2.37
2093
1710
2.54
2272
1756
2.70
2467
1779
3.13
2848
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Indoor-Fan Motor Performance
table on page 52 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.8
Rpm
Bhp
Watts
Rpm
1248
1.20
1081
1322
1356
1266
1.29
1158
1303
1.41
1258
1397
1340
1.53
1361
1428
1375
1.63
1447
1459
1410
1.72
1526
1488
1460
1.90
1683
1532
1518
2.16
1910
1575
1562
2.42
2136
1620
1602
2.64
2326
1666
1642
2.86
2512
1775
1753
3.58
3262
1767
3.69
3360
0.8
Rpm
Bhp
Watts
Rpm
1607
1.94
1761
1667
1621
2.06
1874
1682
1655
2.23
2029
1717
1694
2.44
2224
1758
1736
2.68
2441
1782
2.87
2616
1.0
Bhp
Watts
1.33
1190
1.47
1310
1.52
1353
1.66
1473
1.80
1595
1.93
1709
2.14
1892
2.35
2076
2.59
2283
2.85
2504
3.62
3290
1.0
Bhp
Watts
2.16
1967
2.30
2093
2.49
2266
2.73
2485
31