Carrier 50TFQ004 Product Data page 29

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
1500
808
0.42
1600
846
0.49
1700
884
0.57
1800
924
0.66
1900
965
0.76
2000
1008
0.87
2100
1051
0.99
2200
1095
1.12
2300
1140
1.26
2400
1185
1.41
2500
1231
1.57
50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
1500
1199
1.19
1600
1263
1.28
1700
1295
1.39
1800
1319
1.52
1900
1343
1.64
2000
1374
1.77
2100
1409
1.91
2200
1442
2.08
2300
1475
2.26
1565
2.47
2400
2500
1596
2.95
LEGEND
— Brake Horsepower Input to Fan
Bhp
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils. See
page 49 for accessory/FIOP static pressure information.
FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
0.4
Watts
Rpm
Bhp
Watts
429
914
0.56
572
501
950
0.64
645
582
983
0.72
736
674
1018
0.82
838
777
1057
0.92
940
889
1096
1.04
1063
1012
1136
1.17
1196
1145
1173
1.30
1328
1288
1210
1.47
1502
1441
1249
1.61
1645
1604
1289
1.78
1819
1.4
Watts
Rpm
Bhp
Watts
1216
1126
1.46
1492
1308
1275
1.49
1523
1420
1351
1.58
1615
1553
1389
1.71
1747
1676
1415
1.80
1891
1809
1438
1.99
2034
1952
1465
2.14
2167
2126
1498
2.30
2350
2310
1554
2.64
2698
2524
1649
2.89
2948
3010
1682
3.45
3522
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
1001
0.69
705
1034
0.78
797
1068
0.88
899
1105
0.98
1001
1143
1.10
1124
1177
1.22
1247
1210
1.35
1380
1245
1.49
1523
1284
1.65
1686
1323
1.80
1860
1363
2.00
2044
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
1250
1.69
1757
1299
1.78
1800
1352
1.80
1850
1435
1.91
1952
1478
2.05
2095
1505
2.21
2258
1533
2.45
2501
1568
2.64
2688
1627
3.03
3091
1726
3.31
3379
1760
3.96
4036
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Indoor-Fan Motor Performance
table on page 52 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
0.8
Rpm
Bhp
Watts
Rpm
1084
0.85
869
1168
1111
0.94
961
1194
1145
1.03
1053
1218
1179
1.13
1155
1246
1212
1.26
1288
1280
1247
1.40
1431
1300
1284
1.54
1574
1347
1322
1.70
1737
1380
1356
1.80
1901
1418
1389
2.03
2074
1456
1424
2.22
2269
1500
1.8
Rpm
Bhp
Watts
Rpm
1301
1.91
1944
1349
1352
2.01
2047
1401
1407
2.03
2070
1459
1494
2.15
2197
1548
1538
2.31
2358
1594
1566
2.49
2542
1624
1596
2.77
2821
1654
1632
2.97
3031
1691
1693
3.42
3486
1755
1.0
Bhp
Watts
1.01
1032
1.11
1134
1.21
1237
1.32
1349
1.43
1461
1.57
1604
1.72
1758
1.89
1931
2.07
2115
2.26
2310
2.45
2504
2.0
Bhp
Watts
2.12
2164
2.23
2280
2.26
2305
2.40
2446
2.57
2625
2.77
2830
3.08
3141
3.31
3375
3.81
3881
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents