Carrier 50TFQ004 Product Data page 39

Single-package standard efficiency rooftop heat pump units 3 to 10 nominal tons
Table of Contents

Advertisement

50TFQ005 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Airflow
0.1
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
514
0.15
158
590
1300
545
0.18
189
615
1400
577
0.21
221
642
1500
609
0.26
273
670
1600
642
0.30
315
699
1700
675
0.36
378
728
1800
709
0.41
431
759
1900
743
0.48
504
790
2000
778
0.55
578
836
50TFQ005 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
Airflow
1.0
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
999 0.66
674
1018 0.67
1300
1025 0.74
756
1058 0.79
1400
1042 0.81
828
1080 0.88
1500
1060 0.88
899
1098 0.96
1600
1080 0.95
971
1117 1.04 1058
1700
1101 1.03
1053
1137 1.12 1139
1800
1122 1.11
1134
1157 1.20 1226
1900
1143 1.21
1237
1179 1.30 1328
1165 1.31
1339
1200 1.40 1431
2000
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 835 to 1185 rpm. All other rpms require field-supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
50TFQ005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
0.2
(Cfm)
Rpm
Bhp
1200
641
0.23
1300
673
0.28
1400
705
0.33
1500
738
0.38
1600
772
0.44
1700
806
0.51
1800
841
0.59
1900
876
0.68
2000
912
0.77
50TFF005 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
1200
1106
0.87
1300
1128
0.91
1400
1139
1.01
1500
1162
1.09
1600
1185
1.20
1700
1215
1.31
1800
1243
1.43
1900
1271
1.56
2000
1298
1.69
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Values include losses for filters, unit casing, and wet coils. See page 49 for
accessory/FIOP static pressure information.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
0.2
0.3
0.20
210
657
0.25
0.23
242
680
0.29
0.27
284
704
0.33
0.31
326
729
0.38
0.36
378
755
0.43
0.42
441
782
0.49
0.48
504
810
0.55
0.55
578
838
0.62
0.62
651
875
0.70
External Static Pressure (in. wg)
1.1
1.2
685
1036 0.68
807
1090 0.84
899
1118 0.95
981
1136 1.04 1063
1153 1.12 1140
1172 1.20 1226
1192 1.29 1318
1214 1.39 1420
1235 1.49 1523
0.4
Watts
Rpm
Bhp
Watts
242
761
0.34
357
294
788
0.39
410
347
817
0.45
473
399
847
0.51
536
462
877
0.58
609
536
908
0.66
693
620
939
0.75
788
714
971
0.84
883
809
1004
0.94
988
1.4
Watts
Rpm
Bhp
Watts
889
1134
0.98
998
930
1183
1.10
1052
1012
1218
1.14
1090
1114
1228
1.24
1186
1226
1250
1.35
1291
1339
1276
1.48
1415
1461
1303
1.61
1540
1594
1330
1.74
1664
1727
1358
1.89
1808
External Static Pressure (in. wg)
0.4
263
723
0.30
315
828 0.42
305
744
0.35
368
849 0.47
347
766
0.39
410
870 0.52
394
788
0.44
462
892 0.58
447
811
0.49
515
913 0.64
510
836
0.55
578
935 0.71
578
860
0.62
651
957 0.78
651
886
0.69
725
980 0.86
730
913
0.77
809
1004 0.94
1.4
695
1073 0.71
756
1109 0.75
858
1121 0.87
832
1159 0.90
971
1175 1.06 1014
1206 1.09 1042
1205 1.19 1138
1258 1.30 1243
1224 1.29 1234
1287 1.45 1387
1241 1.38 1320
1307 1.56 1492
1258 1.48 1415
1323 1.67 1597
1279 1.58 1511
1341 1.78 1702
1300 1.69 1616
1361 1.90 1817
3. Maximum usable watts input is 1000 and maximum continuous bhp is 1.00.
Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors up
to the wattage ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional information on
motor performance, refer to Indoor-Fan Motor Performance table on page 52.
4. Values include losses for filters, unit casing, and wet coils. See page 49 for
accessory/FIOP static pressure information.
5. Interpolation is permissible. Do not extrapolate.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier rep-
resentative for details.
External Static Pressure (in. wg)
0.6
Rpm
Bhp
Watts
859
0.46
483
887
0.52
546
914
0.59
620
940
0.65
683
967
0.73
767
997
0.81
851
1026
0.91
956
1056
1.01
1061
1087
1.12
1177
External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
1189
1.12
1138
1226
1.23
1215
1286
1.34
1282
1303
1.40
1339
1319
1.51
1444
1334
1.64
1569
1359
1.78
1702
1386
1.93
1846
1413
2.08
1989
3. Maximum continuous bhp is 2.4 and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors up
to the wattage ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Indoor-Fan Motor Perfor-
mance table on page 52 for additional information.
4. Interpolation is permissible. Do not extrapolate.
5. Use of a field-supplied motor may affect wire sizing. Contact your Carrier rep-
resentative for details.
0.6
0.7
441
876 0.49
510
494
895 0.54
562
546
915 0.59
620
609
936 0.65
683
672
957 0.72
751
746
979 0.79
825
820
1001 0.86
904
904
1023 0.95
993
988
1046 1.03 1082
1.6
1.8
794
1138 0.79
851
918
1193 0.95
976
1244 1.12 1138
1289 1.34 1282
1337 1.56 1492
1366 1.73 1655
1385 1.86 1779
1402 1.98 1894
1419 2.10 2008
0.8
Rpm
Bhp
Watts
Rpm
943
0.58
609
1030
968
0.65
683
1044
996
0.72
757
1069
1095
1024
0.81
851
1051
0.89
935
1123
1077
1.01
1030
1151
1104
1.07
1124
1178
1132
1.18
1240
1204
1162
1.30
1366
1231
1.8
Rpm
Bhp
Watts
Rpm
1245
1.21
1358
1292
1297
1.35
1406
1346
1320
1.48
1463
1370
1343
1.60
1530
1393
1382
1.68
1607
1434
1398
1.80
1722
1451
1418
1.95
1865
1471
1439
2.11
2018
1493
1466
2.27
2171
0.8
924 0.55
578
940 0.60
630
959 0.66
693
980 0.72
757
1001 0.79
830
1023 0.86
904
1044 0.94
988
1066 1.03 1082
1088 1.12 1177
1.0
Bhp
Watts
0.70
695
0.77
736
0.86
838
0.95
930
1.05
1073
1.15
1185
1.26
1318
1.37
1502
1.48
1604
2.0
Bhp
Watts
1.35
1345
1.51
1500
1.65
1645
1.79
1778
1.88
1867
2.01
2001
2.18
2167
2.36
2345
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents