1. Top Vent - Horizontal Termination - (continued)
Three Elbows
WARNING! Risk of Fire!
• LUX36 requires a minimum of 24 inches of vertical venting before
attaching any elbow to the appliance.
• LUX42 requires a minimum of 48 inches of vertical venting before
attaching any elbow to the appliance.
DO NOT attach elbow directly to the appliance.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
V
H
Maximum
1
1
2 ft
610 mm
17 in
3 ft
914 mm
2 ft
4 ft
1.2 m
4 ft
5 ft
1.5 m
9 ft
6 ft
1.8 m
12 ft
7 ft
2.1 m
14 ft
10 ft
3.0 m
20 ft
V
+ H
must be adhered to.
1
1
* V
has no specifi c restrictions EXCEPT,
2
V
+ H
cannot exceed 60 ft Maximum
total
total
Figure 7.5
H
2
V
LUX36
V
H
2
2
432 mm
*
H
Max = 2 X V
2
610 mm
*
H
Max = 2 X V
2
1.2 m
*
H
Max = 2 X V
2
2.7 m
*
H
Max = 2 X V
2
3.7 m
*
H
Max = 2 X V
2
4.3 m
*
H
Max = 2 X V
2
6.1 m
*
H
Max = 2 X V
2
Heat & Glo •
LUX36, LUX42 • 2287-900
2
H
1
V
1
4 ft
1.2 m
2
5 ft
1.5 m
2
6 ft
1.8 m
2
7 ft
2.1 m
2
10 ft
3.0 m
2
2
* V
2
2
V
total
• 2287-900 Rev. J
Rev. J
V
1
LUX42
H
Maximum
V
1
2
17 in
432 mm
*
2 ft
610 mm
*
9 ft
2.7 m
*
14 ft
4.3 m
*
20 ft
6.1 m
*
V
+ H
must be adhered to.
1
1
has no specifi c restrictions EXCEPT,
+ H
cannot exceed 60 ft Maximum
total
• 6/13
H
2
H
Max = 2 X V
2
2
H
Max = 2 X V
2
2
H
Max = 2 X V
2
2
H
Max = 2 X V
2
2
H
Max = 2 X V
2
2
29