Heat & Glo LUX36 Owner's Manual page 28

Hide thumbs Also See for LUX36:
Table of Contents

Advertisement

Two Elbows
WARNING! Risk of Fire!
• LUX36 requires a minimum of 36 inches of vertical venting before
attaching any elbow to the appliance for the venting confi guration
in Figure 7.4.
• LUX42 requires a minimum of 48 inches of vertical venting before
attaching any elbow to the appliance.
DO NOT attach elbow directly to the appliance.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
V
Minimum
1
3 ft
4 ft
5 ft
6 ft
7 ft
8 ft
9 ft
10 ft
V
Figure 7.4
28
H
2
INSTALLED
HORIZONTALLY
LUX36
H
+ H
1
2
914 mm
18 in
457 mm
1.2 m
3 ft
914 mm
1.5 m
7 ft
2.1 m
1.8 m
10 ft
3.0 m
2.1 m
14 ft
3.7 m
2.4 m
16 ft
2.7 m
18 ft
5.5 m
3.0 m
20 ft
6.1 m
+ H
+ H
= 60 ft Maximum
1
1
2
H
+ H
= 20 ft Maximum
1
2
Heat & Glo •
LUX36, LUX42 • 2287-900 Rev. J
H
1
V
Minimum
1
4 ft
5 ft
6 ft
7 ft
8 ft
4.9
9 ft
10 ft
V
+ H
1
H
• 2287-900 Rev. J
V
1
LUX42
H
+ H
1
2
1.2 m
17 in
432 mm
1.5 m
2 ft
610 mm
1.8 m
9 ft
2.7 m
2.1 m
14 ft
3.7 m
2.4 m
16 ft
4.9 m
2.7 m
18 ft
5.5 m
3.0 m
20 ft
6.1 m
+ H
= 60 ft Maximum
1
2
+ H
= 20 ft Maximum
1
2
• 6/13