FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS

SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
one 90
elbow).
o
Note: Must use optional fl ue adapter (Part # 510-994) when using Simpson Dura-Vent pipe.
Maintain clearances to combustibles as listed in section "Clearances."
Horizontal fl ue must be supported every 3 feet (0.9 meters).
Firestops are required at each fl oor level and whenever passing through a wall.
Regency
P36-5 Gas Log Fireplace
®
REGENCY
DIRECT VENT SYSTEM (FLEX)
®
(LPG & NG)
INSTALLATION
o
elbow (two 45
o
elbows equal
Simpson Dura-Vent
4" (102mm) inner diameter
6-5/8" (168mm) outer diameter
Regency
Flex Vent
®
4" (102mm) inner diameter
6-7/8" (175mm) outer diameter
A fl ue guard should be used whenever
the termination is lower than the
specifi ed minimum or as per local
codes.
Note: Regency
®
Co Axial Flue System
(Flex) is only approved for
horizontal terminations.