Matching The Utility Voltage - HP R12000 XR Maintenance And Service Manual

Table of Contents

Advertisement

Identifying Components

Matching the Utility Voltage

Use configuration parameters to select the UPS voltage range (see Table 3-1).
If the utility voltage is within this range, the UPS supplies utility power to the output
receptacles.
If the utility voltage is outside this range, the UPS supplies battery power to the output
receptacles.
If the utility voltage frequently varies outside the operating range, update the UPS
configuration to match.
NOTE: When you set the voltage through the LCD panel (as described in the "Setting the Voltage"
section of this chapter), you are setting the UPS output voltage.
Table 3-1: Voltage Ranges (VAC)
Nominal Utility
Voltage Level
200
208
220
230 (default)
240
To update the configuration:
1. Have a licensed electrician measure your utility voltage.
2. Use Table 3-1 to identify the operating range that most closely matches your nominal
utility voltage level.
3. Update the UPS output voltage as required. Refer to the section, "Setting the Voltage," in
this chapter for more information.
3-8
HP CONFIDENTIAL Codename: Sierra Part Number: 221273-001 Last Saved On: 7/31/02 8:58 AM
Normal Utility
UPS Output
Voltage Range
Voltage
166-240
200
166-248
208
176-264
220
184-276
230
192-288
240
HP UPS R12000 XR Models Maintenance and Service Guide