Flue Collar Reversal; Chimney Connector; Chimney Requirements; Masonry Chimneys - Jøtul F 400 USA Installation And Operating Instructions Manual

Table of Contents

Advertisement

USA/Canada

1.2 Flue Collar Reversal

The Flue Collar is oriented in the Top Exit position. If a Rear Exit
position is required, remove the two mounting bolts, and turn
the collar 180 degrees. Secure the collar using the same bolts,
nuts and washers.

1.3 Chimney Connector

Use 6" single wall or listed 6" double-wall stovepipe to connect the
stove to the chimney. Single wall stovepipe must be black iron or
stainless steel and have a minimum thickness of 24 gauge. Do not
use aluminum or galvanized steel pipe for chimney connection
- these materials are not suitable for use with solid fuel.
Follow these guidelines regarding chimney connector
construction:
NOTE: If a rear heat shield is to be used on the stove, install
it before attaching the chimney connector to the flue collar.
Do not use chimney connector as a chimney. It is intended
only for use as a connection device.
Each connector section must be oriented with the male
(crimped) end pointing toward the stove. See fig. 2.
Secure all connector joints with three sheet metal screws.
For the best performance, the chimney connector should be
as short and direct as possible, including no more than two
90° elbows.
The maximum vertical run of single wall stovepipe should not
exceed 10 ft. (305 cm). The maximum horizontal run should
not exceed 3 ft. (92 cm) with a 1/4" rise per foot.
No part of the chimney connector may pass through an attic
or roof space, closet or other concealed space, or through
a floor or ceiling. All sections of the chimney connectors
must be accessible for cleaning. Where passage through a
wall or partition of combustible construction is desired, the
installation must conform with NFPA 211 or CAN/CSA-B365,
and is also addressed in this manual.
Do not connect this stove to a chimney flue servicing another
appliance.
4

2.0 Chimney Requirements

There are two types of chimneys suitable for the Jøtul F 400 :
1. A code-approved masonry chimney with a ceramic tile or
listed steel flue liner.
2. A prefabricated chimney complying with the requirements
for Type HT (2100°F) chimneys per UL 103 or ULC S629.
The chimney size should not be less than the cross-sectional area
of the flue collar, and not more than three times greater than the
cross-sectional area of the flue collar.
When selecting a chimney type and the location for the chimney
in the house, keep this in mind: It is the chimney that makes the
stove work, not the stove that makes the chimney work. This is
because a chimney actually creates a suction, called "draft" which
pulls air through the stove.
Several factors affect draft: chimney height, cross-sectional area
(size), and temperature of the chimney, as well as the proximity
of surrounding trees or buildings.
A short masonry chimney on the exterior of a house will give
the poorest performance. This is because it can be very difficult
to warm the chimney thereby creating inadequate draft. In
extremely cold climates, it may be necessary to reline the chimney
or extend its height to help establish draft.
A tall, interior masonry chimney is easier to keep warm and will
perform the best under a variety of weather and environmental
conditions.
The following guidelines give the necessary chimney requirements
based on the national code (ANSI-NFPA 211 for the US. And CSA
CAN-B365 for Canada). However, many local codes differ from
the national code to take into account climate, altitude, or other
factors. Your local building inspector is the final approving
authority. Consult them prior to installation.
Do not connect the stove to any air distribution duct or
system.

2.1 Masonry Chimneys

When installing the Jøtul F 400 into a masonry chimney you
must conform to all of the following guidelines:
The chimney flue size should not be less than the cross-
sectional area of the stove flue collar.
The cross-sectional area of the flue of a chimney with no
walls exposed to the outside below the roofline shall not be
more than three times the crosssectional area of the stove
flue collar.
The cross-sectional area of the flue of a chimney with one or
more walls exposed to the outside below the roofline shall
not be more than two times the cross-sectional area of the
stove flue collar.
Larger chimney flues should be relined with a listed or
codeapproved liner.
The masonry chimney must have a fireclay liner or equivalent,
with a minimum thickness of 5/8" (14 mm) and must be
installed with refractory mortar. There must be at least 1/2"
(12.7 mm) air space between the flue liner and chimney wall.
The fireclay flue liner must have a nominal size of 8" X 8" (20
cm x 20 cm), and should not be larger than 8"X 12" (20 cm x
30 cm). A round fireclay liner must have a minimum inside
diameter of 6" (15 cm) and maximum inside diameter of 8" (20
cm). A larger chimney should be relined with an appropriate
code approved liner.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F 400

Table of Contents