Required Tools For Installation Work; Refrigerant Piping Connection; Flaring; Tightening Connection - Toshiba RAS-10YKH-E Service Manual

Split wall type air-conditioner
Table of Contents

Advertisement

CAUTION
Installation in the following places may result in
trouble. Do not install the unit in such places.
• A place full of machine oil.
• A saline place such as coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from radio equipment,
welders, and medical equipment.

8-5-1. Required Tools for Installation Work

1) Philips screw driver
2) Hole core drill (65mm)
3) Gaugramanifold
4) Spanner
5) Pipe cutter
6) Knife
7) Reamer
8) Gas leak detector
9) Tape measure
10) Thermometer
11) Mega-tester
12) Electro circuit tester
13) Vacuum pump
14) Hexagonal wrench (5mm)
15) Torque wrench

8-5-2. Refrigerant Piping Connection

<Flaring>
(1) Cut the pipe with a pipe cutter.
90˚
(2) Insert a flare nut into the pipe, and flare the pipe.
A (mm) R22
Outer
dia.
Imperial
6,35mm
1,0 ~ 1,5
9,52mm
1,0 ~ 1,5
12,7mm
1,5 ~ 2,0
Die
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.
Then tighten the nut with a spanner and torque
wrench as shown in the figure.
CAUTION
• Do not apply excess torque. Otherwise, the
nut may crack depending on the installation
conditions.
Outer dia.
6,35mm
9,52mm
12,7mm
Half union or packed valve
Externally
threaded
side
Use a wrench
to secure.
– 37 –
Obliquity
Roughness
Fig. 8-5-2
A (mm) R410A
Rigid
Imperial
Rigid
0,5 ~ 1,0
1,5 ~ 2,0
1,0 ~ 1,5
0,5 ~ 1,0
1,5 ~ 2,0
1,0 ~ 1,5
0,5 ~ 1,1
A
Pipe
Fig. 8-5-3
Tightening touque
N•m (kgf•m)
16 ~ 18 (1,6 ~ 1,8)
30 ~ 42 (3,0 ~ 4,2)
50 ~ 62 (5,0 ~ 6,2)
Flare nut
Internally
threaded
side
Use a torque wrench
to tighten.
Fig. 8-5-4
Warp