Cord Heater Installation Work; Required Parts For Installation Work (Recommendation) - Toshiba RAS-10JKVP-E Service Manual

Hide thumbs Also See for RAS-10JKVP-E:
Table of Contents

Advertisement

Cord Heater Installation Work

Applicable Models: RAS-10JAVP-E, RAS-13JAVP-E

1. Required parts for installation work (Recommendation)

No.
Part name
Q'ty
1
Cord heater
2
Thermostat
3
Fuse
4
Fuse holder
5
P-shape clamp
16
6
Screw
15
7
Screw
8
Screw
9
Faston
10
Sleeve for Faston
11
Close-end
connector
12
Power cord
13
Thermostat fixing
plate
NOTE: The parts on the above table are recommended parts.
Specifications/Vendor
1
Drain line heaters CSC2 (1.5m, 40W/m) by Flexelec com.
(Please go to the following URL.)
http://www.flexelec.com
1
US-622AXRLQE by ASAHI KEIKI
Operating temperature: on 4 ± 4°C, off 15 ± 3°C
A thermostat holder is incorporated with a thermostat in the
package. (Please go to the following URL.)
http://www.asahikeiki.co.jp/product/product.html
On self-responsibility, you can use a product manufactured by
other company (For example, Texas Instruments) if its character-
istics are equivalent to those of ASAHI KEIKI. However, when the
shape of the thermostat holder is different from that of ASAHI
KEIKI, apply some treatment to No.13 themostat fixing plate and
then fix the holder.
1
ES3-5000, 250V / 5A by NAGASAWA Electric Co.
(Please go to the following URL.)
http://www.nagasawa-el.co.jp/
On self-responsibility, you can use a product manufactured by
other company if its characteristics are equivalent to those of
NAGASAWA Electric Co.
1
GM1H-02 by NAGASAWA Electric Co.
(Please go to the following URL.)
http://www.nagasawa-el.co.jp/
On self-responsibility, you can use a product manufactured by
other company if its characteristics are equivalent to those of
NAGASAWA Electric Co.
Use heat-resistance, weatherproof and non-hydrolytic type.
Material: 4-fluorinated ethylene copolymer
Harness diameter: Ø7.5
Use equivalence with the above specifications.
15 pieces are used to fix the cord heater to the outdoor unit base.
One piece is used to fix the power cords to the thermostat fixing
plate.
Self-tapping screw type-B Ø4 × 6mm, truss head, stainless
These screws are used to fix the cord heater to the outdoor unit
base with P-shape clamp.
3
Self-tapping screw type-B Ø4 × 8mm, truss head, stainless
Two screws are used to fix the thermostat fixing plate to the back
cabinet.
One screw is used to fix the power cord to the thermostat fixing
plate.
2
Self-tapping screw type-B Ø3.5 × 8mm, pan head
These screws are used to fix the thermostat to the thermostat
fixing plate with the thermostat holder.
2
#250
They are used for the connecting part to the thermostat.
2
UL sleeve for #250
2
Use the most appropriate connector with the power cord diameter.
1
2-cores x 0.75mm² or more, H05RN-F
1
Material: SGCC-Z08, Board thickness: 0.8t
Appendix-1
Appendix
Remarks
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
Procured locally
(Drawing attached)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ras-10javp-eRas-13jkvp-eRas-13javp-e

Table of Contents