Toshiba RAS-10YKH-E Service Manual page 12

Split wall type air-conditioner
Table of Contents

Advertisement

4-2. Outdoor Unit
RAS-10YAH-E, RAS-10YAH-ES
RAS-13YAH-E, RAS-13YAH-ES
No.
PARTS NAME
1
Compressor
Fan motor
2
(for outdoor)
Running
3
capacitor
(for fan motor)
Running
4
capacitor
(for compressor)
5
Overload relay
Thermostat
6
(for compressor)
Solenoid coil
7
(for 4-way valve)
MODELS
TYPE
RAS-10YAH-E
PH120T1-4C
RAS-13YAH-E
PH170T2-4L2
RAS-10YAH-ES
PA118X1T-4FZ
RAS-13YAH-ES
PA160X2T-4FM
RAS-10YAH-E
UE6-21SJ5P
RAS-10YAH-ES
RAS-13YAH-E
AF-230-28P
RAS-13YAH-ES
RAS-10YAH-E
SK-50FMP1,5U1
RAS-10YAH-ES
RAS-13YAH-E
SK-50FMP1,5U2
RAS-13YAH-ES
RAS-10YAH-E
SK-40CMP25U1
RAS-10YAH-ES
RAS-13YAH-E
SK-40CMP35U1
RAS-13YAH-ES
RAS-10YAH-E
JMRA99269-9200
RAS-13YAH-E
JMRA99257-9200
RAS-10YAH-E
CS-7
RAS-10YAH-E
LB60012
RAS-13YAH-E
RAS-10YAH-ES
VHV-01A1501A1
RAS-13YAH-ES
Output (Rated) 750W, 2poles, 1phase, 220–240V, 50Hz
Winding resistance ( W )
(at 20°C)
Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz
Winding resistance (W)
(at 20°C)
Output (Rated) 750W, 2poles, 1phase, 220–240V, 50Hz
Winding resistance (W)
(at 20°C)
Output (Rated) 1100W, 2poles, 1phase, 220–240V, 50Hz
Winding resistance ( W )
(at 20°C)
Output (Rated) 18W, 6poles, 1phase, 220–240V, 50Hz
Winding resistance (W)
(at 20°C)
Output (Rated) 28W, 6poles, 1phase, 220–240V, 50Hz
Winding resistance (W)
(at 20°C)
AC 500V, 1,5mF
AC 500V, 1,5 m F
AC 400V, 25mF
AC 400V, 35 m F
U/T : 6,8A (90°C), OPEN 135 ± 5°C, CLOSE : 69 ± 11°C
U/T : 8,0A (80°C), OPEN 145 ± 5°C, CLOSE : 75 ± 11°C
OFF : 130°C, ON : 70°C
AC 200 / 240V
AC 200 / 240V
– 12 –
SPECIFICATIONS
C-R
4,53
C-R
2,22
C-R
3,17
C-R
2,26
Red-Black
White-Black
370
Red-Black
White-Black
198
C-S
8,73
C-S
3,04
C-S
5,18
C-S
3,53
370
160

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents