INSTALLATION MANUAL
AIR CONDITIONER (SPLIT TYPE)
Indoor unit
RAS-B07, 10, 13, 16J2KVSG-E
Outdoor unit
RAS-07, 10, 13, 16J2AVSG-E
R32
ENGLISH
1 1 1 8 3 5 0 1 8 2

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAS-16J2AVSG-E

  • Page 1 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) Indoor unit RAS-B07, 10, 13, 16J2KVSG-E Outdoor unit RAS-07, 10, 13, 16J2AVSG-E 1 1 1 8 3 5 0 1 8 2...
  • Page 2: Table Of Contents

    CONTENTS PRECAUTIONS FOR SAFETY ............................1 ACCESSORY PARTS .................................5 INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS ................................6 Optional Installation Parts ..............................6 INDOOR UNIT ..................................7 Installation Place ................................7 Cutting a Hole and Mounting Installation Plate ........................7 How to Connect Remote Controller for Wire Operation ....................7 Piping and Drain Hose Installation ...........................8 Indoor Unit Fixing ................................9 Drainage ...................................9...
  • Page 3: Precautions For Safety

    PRECAUTIONS FOR SAFETY PRECAUTIONS FOR SAFETY Read the precautions in this manual carefully before This appliance is fi lled with R32. operating the unit. • Before installation, please read these precautions for safety carefully. • Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown below.
  • Page 4 DANGER • FOR USE BY QUALIFIED PERSONS ONLY. • TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. • CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
  • Page 5 • Do not use any refrigerant different from the one specifi ed for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
  • Page 6 CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. •...
  • Page 7: Accessory Parts

    Installation plate × 1 Wireless remote control × 1 Battery × 2 Remote control holder × 1 Toshiba Ultra pure fi lter × 2 Mounting screw × 6 Flat head wood screw × 2 Owner’s Manual × 1 Installation Manual × 1 Flat head wood screw ×...
  • Page 8: Installation Diagram Of Indoor And Outdoor Units

    INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS For the rear left, bottom left and left piping Wall Hook Installation Cut out a piece of SPACER from indoor plate unit packaging box, roll it and insert between the indoor unit and wall to tilt Flat head the indoor unit for better operation.
  • Page 9: Indoor Unit

    INDOOR UNIT INDOOR UNIT When the installation plate is directly mounted Installation Place on the wall • A place which provides the spaces around the indoor unit as shown in the 1. Securely fi t the installation plate onto the wall by screwing it in the upper and diagram lower parts to hook up the indoor unit.
  • Page 10: Piping And Drain Hose Installation

    Front panel Control wire Screw (Ø3.1×16L) for hang remote Hole for hang remote controller controller Control wire Remote controller Wall Screw Screw Remote controller Screw (Ø3.1×25L) Screw cap for fi x battery cover 70 mm * Wire size 28-22AWG or 0.08-0.32 mm Outer diameter not over 4.7 mm, control wire length 30 m.
  • Page 11: Indoor Unit Fixing

    How to remove the drain hose NOTE • The drain hose can be removed by removing the If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. screw securing the drain hose and then pulling out After passing the connecting pipe through the pipe hole, connect the the drain hose.
  • Page 12: Outdoor Unit

    • The allowable length of the connecting pipe. wind waves are likely to be generated as from audio equipment, welders, Model RAS-07J2AVSG-E RAS-10J2AVSG-E RAS-13J2AVSG-E RAS-16J2AVSG-E and medical equipment Chargeless up to 15 m up to 15 m up to 15 m...
  • Page 13: Evacuating

    Tightening connection Compound pressure gauge Pressure gauge –101 kPa Align the centers of the connecting pipes and tighten the fl are nut as far as pos- (–76 cmHg) Manifold valve sible with your fi ngers. Then tighten the nut with a spanner and torque wrench as shown in the fi...
  • Page 14: Electrical Works

    ELECTRICAL WORKS ELECTRICAL WORKS Model RAS-B07J2KVSG-E RAS-B10J2KVSG-E RAS-B13J2KVSG-E RAS-B16J2KVSG-E Power source 50Hz, 220 – 240 V Single phase Maximum running current 4.50A 6.75A 7.50A 9.50A Circuit breaker rating Power supply cable H07RN-F or 60245 IEC66 H07RN-F or 60245 IEC66 (1.5 mm or more) (2.5 mm or more)
  • Page 15: In Case Of Indoor Unit Connect With 1:1 Outdoor Unit

    In Case of Indoor Unit Connect With 1:1 Outdoor Unit Power Supply Input at Outdoor Unit Terminal Block (Recommend) Indoor Unit Outdoor Unit Connecting cable Stripping length of the Connecting cable connect to 1 2 3 Terminal block connecting cable Terminal block (L N 1 2 3) Earth line 50 mm...
  • Page 16 Power supply input Wiring Diagram for 1:1 Outdoor Unit Power input at Outdoor Terminal Block (Recommend) Indoor Chassis Terminal Block Chassis Outdoor Terminal Block Power input Power input at Indoor Terminal Block (Optional) Indoor Chassis Terminal Block Power input Chassis Outdoor Terminal Block...
  • Page 17: In Case Of Indoor Unit Connect With Inverter Multi System (Ims)

    In Case of Indoor Unit Connect With Inverter Multi System (IMS) Power Supply Input at Outdoor Unit Terminal Block Indoor Unit Outdoor Unit Stripping length of the Connecting cable Connecting cable Terminal block connect to 1 2 3 Connecting cable 1(L) Terminal block (L N 1 2 3) Earth line...
  • Page 18: Others

    OTHERS OTHERS Gas Leak Test Test Operation To switch the TEST RUN (COOL) mode, press [RESET] button for 10 seconds. (The beeper will make a short beep.) Check places for the indoor unit. OPERATION / RESET Button Check places for the outdoor unit.