Power Factor Correct Of Pfc Faulr - Toyotomi GAN-A135GVR-T3 Service Manual

Table of Contents

Advertisement

Start
Check wiring of the
reactor (L) of the
outdoor unit and the
PFC capacitor
Whether there is any
damage or
short-circuit?
N
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
N
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the
reactor by an ohm gauge
Whether there is any damage
or short-circuit?
N
Replace the control
panel AP1
End
Replace it as per the
wiring diagram and
Y
reconnect the wires
The capacitor is
short circuited and
Y
the capacitor
should be repla-
ced
Replace the reactor
Y
If the fault is eliminated?
N
Restart the unit
If the fault is eliminated?
N
If the fault is eliminated?
Restart the unit
N
Y
Y
Y