Outdoor Grill Installation
Natural Gas Installations
The natural gas pressure regulator provided with natural
gas outdoor products is set for 4"
column) and is for use with natural gas only.
NATURAL GAS SAFETY REQUIREMENT
This gas appliance and its individual shut-off valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test pres-
sures greater than .5 psi
This gas appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than .5 psi
.
(3.5 kPa)
NATURAL GAS CONNECTION
A typical natural gas installation is shown in the illustra-
tions below. Make sure that the gas pressure regulator(s)
supplied with the outdoor product is used and installed
with the arrow on the regulator pointing towards the unit.
Do not use a replacement regulator other than that speci-
fied by Wolf. Use only gas piping that is approved for use
with natural and LP gases.
REGULATOR
REAR GAS
CONNECTION
BOTTOM GAS
CONNECTION
SHUT-OFF
VALVE
Natural gas connection.
WC (water
(10 mb)
.
(3.5 kPa)
ADAPTER
VENT
CLOSE
NIPPLE
TO GRILL
REGULATOR
Natural gas regulator.
LP Gas Installations
LP (liquefied petroleum) gas is sometimes called propane,
butane or bottled gas. It is a flammable gas which
becomes liquid when stored under high pressure inside a
cylinder and it vaporizes when released.
The LP gas pressure regulator and hose provided with
LP outdoor gas grills (except model OG54) and SB13-LP
is set for 11"
LP gas only and a 20-lb LP gas cylinder. The LP gas regu-
lator provided with OG54-LP and BM13-LP is set for 10"
WC.
(25 mb)
LP GAS SAFETY REQUIREMENT
The LP gas cylinder must be provided with an approved
overfilling preventive device (OPD).
Any LP gas cylinder used with this appliance must be
constructed and marked in accordance with the specifica-
tions for LP gas cylinders of the U.S. Department of Trans-
portation (D.O.T.) or the National Standards of Canada
CAN/CSA-B339, Cylinders, Spheres and Tubes for the
Transportation of Dangerous Goods and Commission, as
applicable. Provided with a listed overfilling prevention
device and a cylinder connection device compatible with
the connection for outdoor cooking appliances.
The LP gas cylinder must be provided with a shut-off valve
terminating in the cylinder valve outlet. It must include a
collar to protect the cylinder valve. The cylinder supply
system must be arranged for vapor withdrawal. Do not use
a cylinder that is dented, rusted or has a damaged valve.
IMPORTANT NOTE: Do not operate the outdoor product
indoors or in any enclosed area. When not in use, the gas
must be turned off at the LP gas cylinder. If the outdoor
product is to be stored indoors, disconnect the cylinder
FROM GAS
SUPPLY
and leave it outdoors.
WC (water column) and is for use with
(27 mb)
11
wolfappliance.com