Options; Generator On Facility; Figure 11-1 Generator On Connection - Powerware 9320 Installation And Operation Manual

10 kva and 20 kva modular ups system
Table of Contents

Advertisement

Options

11.1 Generator ON Facility

The generator ON facility must use a normally open contact that closes to indicate that a
generator is running and supplying input power to the UPS. When used, this facility
disables the UPS static bypass and prevents the UPS from transferring the load into the
generator power supply. The user may also elect prevention of battery charging while
on generator input. Both or either of these features may be selected via the control
panel. (See section 7.3.8, Set Up)
UPS Generator
port (X2)
Powerware 9320 (10 kVA and 20 kVA) Installation and Operation
164201416 REV. A 071103
Figure 11–1. Generator ON Connection
11
Generator alarm panel
11-1

Advertisement

Table of Contents
loading

Table of Contents