CAUTION:
ACTIVATION OF THE ON/OFF PUSHBUTTONS WHEN THE UPS IS NOT IN
MAINTENANCE BYPASS MODE WILL INTERRUPT THE POWER SUPPLY TO
THE CRITICAL LOAD.
If, for security or emergency reasons, it is necessary to immediately disconnect the load
from the UPS, press the two red ON/OFF pushbuttons simultaneously. In this case,
make sure that the maintenance bypass switch (IA1) is in the "O" position (Normal=Off).

7.3 Description of the LCD Screen

7.3.1 Status Screens

DESCRIPTION
Load is protected by UPS power. It is
supplied by the inverter (normal operation)
Load is not protected by UPS power. It is
supplied by utility power. (load on bypass)
Load supply is completely interrupted. UPS
has been switched off by "ON/OFF" buttons
NOTE:
S
P01
P02
P03
7-4
On the right hand side of the LCD there is a 3 digit indicator defining the
Module "Position" in the Multi-Module system.
stands for Single Module. The system consists only of one Module.
stands for Parallel Module in a Multi-Module system and 01 stands for the
first Module (MASTER) in the Multi-Module system.
stands for Parallel Module in a Multi-Module system and 02 stands for the
second Module (SLAVE) in the Multi-Module system.
stands for Parallel Module in a Multi-Module system and 03 stands for the
third Module (SLAVE) in the Multi-Module system.
LCD DISPLAY
LOAD
PROTECTED
LOAD
NOT PROTECTED
LOAD OFF
SUPPLY FAILURE
Powerware 9320 (10 kVA and 20 kVA) Installation and Operation
P01
P01
P01
164201416 REV A 071103