Table 16 – Altitude Derate Multiplier for USA.
ALTITUDE
PERCENT OF
FT (M)
DERATE
0–2000
0
(0 --- 610)
2001–3000
4---6
(610 --- 914)
3001–4000
6---8
(914 --- 1219)
4001–5000
8---10
(1219 --- 1524)
5001–6000
10---12
1524 --- 1829)
6001–7000
12---14
(1829 --- 2134)
7001–8000
14---16
(2134 --- 2438)
8001–9000
16---18
(2438 --- 2743)
9001–10,000
18---20
(2743 --- 3048)
* Derate multiplier factors are based on midpoint altitude for altitude range.
Table 17 – Gas Rate (CU FT/HR)
SIZE OF TEST
SECONDS
DIAL
FOR 1
REVOLUTION
1
2
5
Cu Ft
Cu Ft
Cu Ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
DERATE MULTIPLIER
FACTOR*
1.00
0.95
0.93
0.91
0.89
0.87
0.85
0.83
0.81
SIZE OF TEST
SECONDS
DIAL
FOR 1
REVOLUTION
1
2
5
Cu Ft
Cu Ft
Cu Ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
124
29
58
145

SET TEMPERATURE RISE

CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the
heat exchangers or condensing flue gases in heat exchanger
areas not designed for condensate.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
Place SW-1 in ON position. Jumper R to W/W1 and W2 to check
high-gas-heat
temperature
temperature rise, remove jumper to W2. Determine air
temperature rise for both high and low gas heat. Do not exceed
temperature rise ranges specified on unit rating plate for high and
low gas heat.
This furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Determine the air
temperature as follows:
a. Place duct thermometers in return and supply ducts as
close to furnace as possible. Be sure thermometers do
not "see" heat exchangers so that radiant heat does not
affect thermometer readings. This is particularly
important with straight run ducts.
b. When thermometer readings stabilize, subtract
return-air temperature from supply-air temperature to
determine temperature rise.
If the temperature rise is outside this range, check the following:
a. Gas input for low-and high gas heat operation.
b. Derate for altitude if applicable.
c. Return and supply ducts for excessive restrictions
causing static pressures greater than 0.50-in. wc.
d. Adjust temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115-v electrical power before changing speed tap.
For high-heat, the following connections can be made at HI
HEAT on control:
a. Med-high (Yellow)
b. Med (Orange) - - Available only on 5-speed motors.
Factory setting for these motors.
c. Med-Low(Blue) - - Do NOT use for HI GAS-HEAT
on 80K & 120K Btuh input models. Factory setting
for 4-speed motors.
59
rise.
To
check
low-gas-heat