Vent Information and Diagrams

A. Vent Guidelines
WARNING
Fire Risk.
Asphyxiation Risk.
This appliance requires the specifi ed pipe for
operation.
• Incorrect pipe may cause spillage, condensation
and overheating.
These models require the following size B-vent double
wall, or single wall rigid or fl ex vent pipe.
Models
SL-550TV-IPI-E
SL-750TV-IPI-E
SL-950TV-IPI-E
• B-vent pipe MUST be used when the vent system is
within combustible construction.
• Single wall rigid or fl exible vent may be used ONLY if the
vent system is installed within non-combustible construc-
tion such as a masonry chimney.
• When installing vent pipe, follow manufacture's installa-
tion instructions.
WARNING
Fire Hazard.
Explosion Risk.
Asphyxiation Risk.
Do NOT connect this gas appliance to a
chimney fl ue serving a separate solid-fuel or
gas burning appliance.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
May impair safe operation of this appliance or
other appliances connected to the fl ue.
B. Vent System Confi guration
CAUTION
ALL vent confi guration specifi cations MUST be followed.
• This product is tested and listed to appliance and vent
manufacturer's specifi cations.
• Appliance performance will suffer if specifi cations are not
followed.
Pipe Size
5 inches
5 inches
6 inches
Heat & Glo • SL-550 / 750 / 950TV-IPI-E • 2119-900 Rev. G • 9/08
Rise to Run Ratio = 2:1
Maximum Total Horizontal Run = 15 Feet
Minimum Total Vertical Rise = 9 Feet
Maximum Total Vertical Rise = 48 Feet
Maximum Number of Elbows: Two 90
Note: A rise of 1/4 inch per foot of horizontal run is required.
9 FEET
MINIMUM
48 FEET
MAXIMUM
Figure 5.1
VE N T S U P P O R T S
A R E P E R V E N T
M A N U F A C T U R E R 'S
S P E C IF IC A T IO N S .
M A X IM U M H O R IZ O N T A L R U N IS 5 0 %
O F V E R T IC A L . H O R IZ O N T A L R U N
C A N N O T B E M O R E T H A N 1 5 F T .
Figure 5.2
0
or Four 45
0
MINIMUM CLEARANCES
ARE PER VENT
MANUFACTURER'S
SPECIFICATIONS
VENT SUPPORTS ARE PER
VENT MANUFACTURER'S
SPECIFICATIONS
M E TA L
P L U M B E R S ' S T R A P