Gas Supply - Empire Comfort Systems DVD32FP34N-1 Installation Instructions And Owner's Manual

Direct vent gas fireplace heater
Table of Contents

Advertisement

The gas pipeline can be brought in through the bottom right or left
side of the appliance. Consult the current National Fuel Gas Code,
ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Nat.
0-10ft
1/2"
0-3m
12.7 mm
11-40ft
1/2"
4-12m
12.7 mm
41-100ft
1/2"
13-30m
12.7 mm
101-150ft
3/4"
31-46m
19 mm
Note: Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a flexible
appliance connector cannot exceed three feet in length.
Gas Supply Pressure (inches w.c.)
Minimum
Natural Gas
LP (Propane)
10.8"
Natural Gas
LP (Propane)
Page 8

GAS SUPPLY

Tubing, Type L
Outside Diameter
L.P.
Nat.
3/8"
1/2"
9.5 mm
12.7 mm
1/2"
5/8"
12.7 mm
15.9 mm
1/2"
3/4"
12.7 mm
19 mm
1/2"
7/8"
12.7 mm
22.2 mm
Figure 6
Normal
Maximum
4.5"
7.0"
14.0"
11.0"
14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
3.5"
10.0"
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
L.P.
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
3/8"
unexposed, a pressure test should be made.
9.5 mm
Never use an exposed flame to check for leaks. Appliance must be
disconnected from piping at inlet of control valve and pipe capped
1/2"
or plugged for pressure test. Never pressure test with appliance
12.7 mm
connected; control valve will sustain damage!
1/2"
NOTE: The millivolt gas controls are equipped with a captured screw
12.7 mm
type pressure test point, therefore it is not necessary to provide a
1/8" test point up stream of the control.
3/4"
1.9 mm
When using copper or flex connector use only approved fittings.
The appliance and it's individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5 kPa).
Attention! If one of the procedures results in pressures in excess of
1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result
in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5" w.c. (.871 kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5" w.c.
(1.120 kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484 kPa). Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49 kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8" w.c.
(2.68 kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484 kPa).
Figure 7
26988-3-1012

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvd36fp34n-1

Table of Contents