Interior Or Exterior Masonry Chimney - Lopi Leyden Owner's Manual

Wood stove
Hide thumbs Also See for Leyden:
Table of Contents

Advertisement

18
Interior or Exterior
Masonry Chimney
NOTE:
This type of installation
requires a UBC approved
masonry connector or
other method approved by
the NFPA 211 standard.
See Chimney Connector
Requirements on page 11
for further details.
© Travis Industries
Stove Installation
NOTE: The chimney must have a
clay tile liner. If it does not, the
installation must use a positive
connection (full reline). The
entire fireplace and chimney must
be clean, undamaged, and meet
all local building codes (UBC,
etc.). Damage must be repaired
prior to installation. The chimney
must be 15' to 33' tall.
See the section "Stove
Placement Requirements" for
minimum clearances required.
Chimney connector sections
See the section
"Floor Protection
Requirements"
(for qualified installers only)
Min. 18"
clearance
to ceiling
100-01177_005
Clay Liner
This type of
installation requires
a UBC approved
masonry connector
or other method
approved by the
NFPA 211 standard.
Full Re-Line
(recommended)
Make sure the
clean-out seals in
place.
Figure 17
4100818