Circulating Air & Filters; Duct Work - Air Flow; Checking Duct Static - Goodman MVM96 Installation Instructions Manual

Modulating gas furnace
Hide thumbs Also See for MVM96:
Table of Contents

Advertisement

Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing Size, O.D. Type L
Tubing
Length
Feet
3/8"
1/2"
10
730
1,700
3,200
20
500
1,100
30
400
920
2,000
40
370
850
1,700
50
330
770
1,500
60
300
700
1,300
80
260
610
1,200
100
220
540
1,000
125
200
490
150
190
430
175
170
400
200
160
380
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length
Feet
3/8"
1/2"
5/8"
10
39
92
199
20
26
62
131
30
21
50
107
40
19
41
90
50
18
37
79
60
16
35
72
80
13
29
62
100
11
26
55
125
10
24
48
150
9
21
43
200
8
19
39
250
8
17
36
*Data in accordance with NFPA pamphlet No. 54
Propane Gas Piping Chart II
C
A
& F
IRCULATING
IR
D
- A
F
UCT WORK
IR
LOW
N
 
 
 
EVER
ALLOW
THE
PRODUCTS
 
 
 
MONOXIDE
TO
ENTER
THE
RETURN
.
SUPPLY
Duct systems and register sizes must be properly designed for
the CFM and external static pressure rating of the furnace. Design
the ductwork in accordance with the recommended methods of
"Air Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the Na-
tional Board of Fire Underwriters for the Installation of Air Condition-
ing, Warm Air Heating and Ventilating Systems. Pamphlets No.
90A and 90B.
Nominal Pipe Size
Schedule 40
5/8"
3/4"
7/8"
1/2"
5,300
8,300
3,200
220
3,700
5,800
2,200
2,900
4,700
1,800
2,700
4,100
1,600
2,400
3,700
1,500
2,200
3,300
1,300
1,900
2,900
1,200
1,700
2,600
1,000
900
1,400
2,300
900
830
1,300
2,100
830
780
1,200
1,900
770
730
1,100
1,800
720
Nominal Pipe Size
Schedule 40
3/4"
7/8"
1/2"
3/4"
1"
1-1/4" 1-1/2"
329
501
275
567
1,071 2,205
216
346
189
393
732
1,496
181
277
152
315
590
1,212
145
233
129
267
504
1,039
131
198
114
237
448
913
1,211
187
103
217
409
834
104
155
89
185
346
724
90
138
78
162
307
630
81
122
69
146
275
567
72
109
63
132
252
511
66
100
54
112
209
439
60
93
48
100
185
390
ILTERS
WARNING
 
 
 
OF
COMBUSTION
INCLUDING
CARBON
 
 
 
 
DUCT
WORK
OR
CIRCULATION
A closed return duct system must be used, with the return duct
connected to the furnace. NOTE: Ductwork must never be at-
tached to the back of the furnace. For upflow installations requir-
ing 1800 CFM or more, use either two side returns or bottom
return or a combination of side /bottom. Flexible joints may be
3/4"
used for supply and return connections to reduce noise transmis-
7,500
sion. To prevent the blower from interfering with combustion air or
4,200
draft when a central return is used, a connecting duct must be
4,000
3,700
installed between the unit and the utility room wall. Never use a
3,400
room, closet, or alcove as a return air chamber.
3,100
2,600
C
D
2,300
HECKING
UCT
2,100
1,900
Refer to your furnace rating plate for the maximum ESP (ex-
1,700
ternal duct static) rating.
1,500
Total external static refers to everything external to the fur-
nace cabinet. Cooling coils, filters, ducts, grilles, registers
must all be considered when reading your total external static
pressure. The supply duct pressure must be read between
the furnace and the cooling coil. This reading is usually taken
by removing the "A" shaped block off plate from the end on the
coil; drilling a test hole in it and reinstalling the block off plate.
Take a duct static reading at the test hole. Tape up the test
hole after your test is complete. The negative pressure must
3,307
be read between the filter and the furnace blower.
2,299
1,858
Too much external static pressure will result in insufficient air
1,559
1,417
that can cause excessive temperature rise. This can cause
1,275
limit switch tripping and heat exchanger failure.
1,066
976
To determine total external duct static pressure, proceed as
866
787
follows;
665
590
1. With clean filters in the furnace, use a draft gauge (in-
clined manometer) to measure the static pressure of the
return duct at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
3. The difference between the two numbers is .4" w.c.
Example:
 
static reading from return duct = -.1" w.c.
 
 
AIR
static reading from supply duct = .3" w.c.
total external static pressure on this system = .4" w.c.
NOTE: Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner
coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include theses components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed dampers,
registers, undersized and/or oversized poorly laid out duct work.
33
S
TATIC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents