Dual Certification : Non -Direct /Direct Vent; Materials And Joining Methods; Proper Vent /Flue And Combustion Air Piping Practices; Termination Locations - Goodman MVM96 Installation Instructions Manual

Modulating gas furnace
Hide thumbs Also See for MVM96:
Table of Contents

Advertisement

It is the responsibility of the installer to follow the manufacturers'
recommendations and to verify that all vent/flue piping and connec-
tors are compatible with furnace flue products. Additionally, it is
the responsibility of the installer to ensure that all piping and con-
nections possess adequate structural integrity and support to pre-
vent flue pipe separation, shifting, or sagging during furnace opera-
tion.
D
C
: N
UAL
ERTIFICATION
ON
This furnace is dual certified and may be installed as a non-direct
vent (single pipe) or direct vent (dual pipe) appliance. A non-direct
vent installation requires only a vent/flue pipe, while a direct vent
installation requires both a vent/flue pipe and a combustion air
intake pipe. Refer to the appropriate section for details concerning
piping size, length, number of elbows, furnace connections, and
terminations.
T
 
 
 
O
AVOID
BODILY
INJURY
FIRE
 
 
 
 
 
MUST
BE
KEPT
AWAY
FROM
ALL
 
 
FLAMES
AND
EXCESSIVE
HEAT
A
 
 
 
VOID
BREATHING
CEMENT
VAPORS
.
EYES
Two- or three-inch nominal diameter PVC Schedule 40 pipe meet-
ing ASTM D1785, PVC primer meeting ASTM F656, and PVC
solvent cement meeting ASTM D2564 specifications must be used.
Fittings must be DWV type fittings meeting ASTM D2665 and
ASTM D3311. Carefully follow the pipe manufacturer's instruc-
tions for cutting, cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC or ABS cellular core (Foam Core)
plastic pipe is also acceptable as a flue/vent and intake pipe mate-
rial. PVC primer meeting ASTM F656 and PVC solvent cement
meeting ASTM D2564 specifications must be used. Fittings must
be DWV type fittings meeting ASTM D2665 and ASTM D3311.
Carefully follow the manufactures instructions for cutting, cleaning
and solvent cementing of PVC.
M
J
M
ATERIALS AND
OINING
ETHODS
As an alternative to PVC pipe, primer, solvent cement, and fittings,
ABS materials which are in compliance with the following specifi-
cations may be used. Two-or-three-inch ABS Schedule 40 pipe
must meet ASTM D1527 and, if used in Canada, must be CSA
listed. Solvent cement for ABS to ABS joints must meet ASTM
D2235 and, if used in Canada, must be CSA listed. The solvent
cement for the PVC to ABS transition joint must meet ASTM D3138.
Fittings must be DWV type fittings meeting ASTM D2661 and
ASTM D3311 and, if used in Canada, must be CSA listed. Care-
fully follow the manufacturers' instructions for cutting, cleaning,
and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long
radius (Long sweep 1/4 bend DWV) types conforming to ASTM
D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/
16" minimum from the plane of one opening to the centerline of the
other opening for 2" diameter pipe, and 4 9/16" minimum for 3"
pipe.
-D
/D
V
IRECT
IRECT
ENT
WARNING
 
 
 
OR
EXPLOSION
SOLVENT
CEMENTS
 
 
 (
.
., 
IGNITION
SOURCES
I
E
SPARKS
 
 
 
 
AS
THEY
ARE
COMBUSTIBLE
LIQUIDS
 
 
 
 
 
OR
CONTACT
WITH
SKIN
AND
P
V
ROPER
ENT
Adhere to these instructions to ensure safe and proper furnace
performance. The length, diameter, and number of elbows of the
vent/flue pipe and combustion air pipe (when applicable) affects
the performance of the furnace and must be carefully sized. All
piping must be installed in accordance with local codes and these
instructions.
Piping must be adequately secured and supported to prohibit sag-
ging, joint separation, and/or detachment from the furnace. Hori-
zontal runs of vent/flue piping must be supported every three to five
feet and must maintain a 1/4 inch per foot downward slope, back
towards the furnace, to properly return condensate to the furnace's
drain system. Allowances should be made for minor expansion
and contraction due to temperature variations. For this reason,
particular care must be taken to secure piping when a long run is
followed by a short offset of less than 40 inches.
Precautions should be taken to prevent condensate from freezing
 
inside the vent/flue pipe and/or at the vent/flue pipe termination. All
 
OPEN
vent/flue piping exposed to temperatures below 35°F for extended
periods of time must be insulated with 1/2" thick closed cell foam.
/
 
OR
Also all vent/flue piping exposed outdoors in excess of the termi-
nations shown in this manual (or in unheated areas) must be insu-
lated with 1/2" thick closed cell foam. Inspect piping for leaks prior
to installing insulation.
T
L
ERMINATION
NOTE: Refer to Location Requirements and Considerations for
combustion air contaminant restrictions.
The following bullets and diagram describe the restrictions con-
cerning the appropriate location of vent/flue pipe and combustion
air intake pipe (when applicable) terminations. Refer to Non-Direct
Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping lo-
cated in this section for specific details on termination construc-
tion.
All terminations (flue and/or intake) must be located at
least 12 inches above ground level or the anticipated snow
level.
Vent terminations (non-direct and direct vent) must
terminate at least 3 feet above any forced air inlet located
within 10 feet.
NOTE: This provision does not apply to the combustion
air intake termination of a direct vent application.
The vent termination of a non-direct vent application must
terminate at least 4 feet below, 4 feet horizontally from,
or 1 foot above any door, window, or gravity air inlet into
any building.
The vent termination of a direct vent application must
terminate at least 12 inches from any opening through
which flue gases may enter a building (door, window, or
gravity air inlet).
The vent termination of vent pipe run vertically through a
roof must terminate at least 12 inches above the roof line
(or the anticipated snow level) and be at least 12 inches
from any vertical wall (including any anticipated snow
build up).
13
/F
C
A
LUE AND
OMBUSTION
IR
OCATIONS
P
P
IPING
RACTICES

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents