To ensure proper unit grounding, the ground wire should run from
the furnace ground screw located inside the furnace junction box
all the way back to the electrical panel. NOTE: Do not use gas
piping as an electrical ground. To confirm proper unit grounding,
turn off the electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection
and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which
interrupts unit voltage when the blower door is opened for servicing.
Do not defeat this switch.
24 V
T
W
OLT
HERMOSTAT
IMPORTANT NOTE
W
IRE
ROUTING
MUST
NOT
INTERFERE
,
OPERATION
FILTER
REMOVAL
A
REMOVABLE
PLUG
CONNECTOR
MAKE
THERMOSTAT
WIRE
CONNECTIONS
WIRE
CONNECTIONS
MADE
TO
STRONGLY
RECOMMENDED
TERMINAL
BE
TWISTED
TOGETHER
. F
CONNECTOR
AILURE
TO
DO
.
OPERATION
IMPORTANT NOTE
D
#13 MUST
IP
SWITCH
BE
SET
CTK01AA
THE
COMMUNICATING
ON
MUST
BE
SET
TO
POSITION
‐
FOR
A
NON
COMMUNICATING
CTK02AA
MODULATING
THERMOSTAT
#13
OFF
SWITCH
IS
IN
THE
POSITION
ALSO
THE
CORRECT
POSITION
‐
.
SINGLE
STAGE
THERMOSTAT
As a two-stage non-communicating furnace, the furnace integrated
control module provides terminals for both "W1" and "W2", and
"Y1" and "Y2" thermostat connections. This allows the furnace to
support the following system applications: 'Two-Stage Heating
Only', 'Two-Stage Heating with Single Stage Cooling', and 'Two-
Stage Heating with Two-Stage Cooling'. Refer to the following fig-
ures for proper connections to the integrated control module.
Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located in the
blower compartment. The following figure shows connections for a
"heat/cool system".
This furnace is equipped with a 40 VA transformer to facilitate use
with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.
NOTE: Use of ramping profiles requires a jumper between Y1
and O.
IRING
WITH
CIRCULATOR
BLOWER
.
OR
ROUTINE
MAINTENANCE
IS
PROVIDED
WITH
THE
CONTROL
. T
HIS
PLUG
MAY
BE
,
. I
THE
PLUG
AND
REPLACED
T
THAT
MULTIPLE
WIRES
INTO
A
PRIOR
TO
INSERTING
INTO
SO
MAY
RESULT
IN
INTERMITTENT
TO
MATCH
THERMOSTAT
TYPE
,
THERMOSTAT
DIP
SWITCH
. T
HIS
IS
ALSO
THE
CORRECT
SETTING
2‐
. T
STAGE
THERMOSTAT
O
USE
,
CHECK
TO
MAKE
SURE
(
). T
FACTORY
POSITION
‐
WHEN
USING
A
NON
COMMUNICATING
T
HERMOSTAT
C
A
OMFORT
C
THE
ONFORT
Low Voltage Connections with Auxiliary Terminals
The auxiliary contacts are shipped with a factory installed
jumper. As an option, the auxiliary contacts may be wired to
a normally closed float switch. In the event of open contacts,
the furnace will be disabled until the condition is corrected.
TO
These are 24 volt terminals fed internally, do not apply another
,
REMOVED
voltage source to these terminals.
IS
SINGLE
THE
PLUG
. T
O SE
U
#13
Thermostat - Single-Stage Heating with Single-Stage Cooling
DIP
HIS
IS
T
O
APPLY
SELECTOR
SET
ON
SINGLE
_________________________________
Thermostat - Two-Stage Heating with Single-Stage Cooling
27
IMPORTANT NOTE
"R"
REQUIRED
IF
OUTDOOR
™
LERT
MODULE
OR
IF
THE
OUTDOOR
N
™
ET
FAMILY
OF
EQUIPMENT
24 V THERMOSTAT CONNECTIONS
R
R
NEU
Y
C
Remote
Condensing Unit
(Single-Stage Cooling)
IMPORTANT NOTE
‐
H
T
A
SINGLE
STAGE
EATING
HERMOSTAT
I
C
SWITCH
ON
THE
NTEGRATED
‐
.
STAGE
R
R
Y
C
NEU
Remote
Condensing Unit
(Single-Stage Cooling)
UNIT
IS
EQUIPPED
WITH
A
UNIT
IS
A
PART
OF
.
AUX
Furnace Integrated
Control Module
Dehumidistat
[Optional]
,
THE
THERMOSTAT
M
MUST
ONTROL
ODULE
BE
____
Furnace Integrated
Control Module
Dehumidistat
[Optional]